weed instrument EOTec 2000 MUX Скачать руководство пользователя страница 1

Safety and Warning Information 

 

Connect the DIN Rail, via the Model 2A09 End 
Clamp, to protective earth ground with low 
impedance.  The modules are grounded to PE 
when they are snapped onto the DIN Rail.  A 
Model 2A09 End Clamp on each side of the 
module bundle on the DIN rail prevents 
accidental disconnection of the modules’ 
interconnection bus. 

Weed Instrument Co., Inc. 

Fiber Optics Division 

 

Phone: 800-880-9333 
 512-434-2850

 

Fax: 512-434-2851

 

Email: 

[email protected]

 

Visit: www.weedinstrument.com 

Important Notice

 - Before utilizing the product, the user should 

determine the suitability of the product for its intended use.  The 
user assumes all risk and liability in connection with such use.  
WEED INSTRUMENT'S WRITTEN WARRANTY FOR THE 
PRODUCT IS MADE IN LIEU OF ALL OTHER WARRANTIES, 
EXPRESSED OR IMPLIED WARRANTIES OF 
MERCHANTABILITY AND FITNESS FOR A PARTICULAR 
PURPOSE.  The user's exclusive remedy for breach of Weed 
Instrument's written warranty shall be the repair or replacement 
of such quantity of product which is proven to be defective.  In no 
case shall Weed Instrument be liable for any special, incidental, 
or consequential damages based upon breach of contract, 
negligence, strict liability or other legal theory. 

Publication Number: 

RM0900177  Rev. 7/04 

Weed Instrument

Fiber Optics

EOTec 2000 MUX Model 

2M30 

Dual Channel, RS-232/485 

Installation Instructions

 

2 Channel, RS-232 or RS-485 

Serial Communications Module 

 

For use with the EOTec 2000 

Multiplexer (MUX) 

Power Requirements 

9VDC @ 200mA via 
the interconnection Bus 
from a 2A06 or 2A16 
power supply or the 
MUX Base Module 
(2M55, 2M57, 2M59 or 
2M61) 

 

Connections 

Pluggable, Cage Clamp 
Screw Terminal Blocks, 
Accept 12 to 24 AWG  

 

Serial Communications  Bi-directional, 

Half-Duplex 

 
Baud Rates 

 

RS-232: 9.6K to 115.2K 

   RS-485: 

9.6K 

to 

230.4K 

 

Wire Cable Termination  

RS-232  

none required 

RS-485  

User supplied based on 
cable specifications 

 

Maximum Devices  
and Cable Length 
 

RS-232 

1 Device, 50ft (15m) 

 

RS-485 

30 Devices, 2000ft 

 

 

 

       (600m)

 

 

Ambient Conditions 

-40 to 85°C 

   0 

to 

95% 

Humidity 

   (Non-condensing) 

 

Mounting 

 

35mm DIN Rail 

 

Weight 

  < 

9oz 

 

Flammability Rating 

UL V-0  

 

Specifications 

Отзывы: