LX3V-4AD
5
WECON TECHNOLOGY CO., LTD.
*#24
Gain Value Default = 5,000
#25-#28
Reserved
#29
Error status
#30
Identification code K2010 (12-bit resolution)
Identification code K2011 (16-bit resolution)
#31
Hardware version
In buffer memory locations (BFM’s) marked with an “*” data can be written from the PC using
the TO command.
For buffer memories (BFM’s) without “*”mark, data can be read to the PC using the FROM
command.
Before reading from the analog special function block, ensure these settings have been sent to
the analog special function block. Otherwise, the previous values held in the analog block will
be used.
Offset (intercept): The analog input value when the digital output becomes 0.
Gain (slope): The analog input value when the digital output b1000.
Note
1)
Channel Selection
Channel initialization is made by a 4 character HEX number HOOOO in buffer memory BFM #0.
The least significant character controls channel 1 and the 4 character controls channel4.
BFM#0
Analog input
Digital output
Resolution
Offset/Gain
Constant
0
-10V~10V
-2000~2000
5 mV
0/5000
1000
1
4mA~20mA
0~1000
16µA
4000/20000
1000
2
-20mA~20mA
-1000~1000
20µA
0/20000
1000
3
Disabled
/
/
/
/
4
-10V~10V
-10000~10000 1mV
0/5000
10000
5
4 mA ~20mA
0~10000
1.6µA
4000/20000
10000
6
-20mA~20mA
-10000~10000 2.0µA
0/20000
10000
Example: H3310
CH1: Preset range (-10V to +10V).
CH2: Preset range (+4mA to +20mA).
CH3, CH4: Channel OFF.
2)
Analog to Digital Conversion Speed Change