LX3V-4AD
2
WECON TECHNOLOGY CO., LTD.
3.
Terminal layouts
4.
Installation
4.1 Environment specification
Item
Specification
Environmental
specifications
(excluding Same as those for the LX3V main unit
Please use crimp terminals as indicated on the
graph.
The tightening torque should be applied 5 to 8
Kg.cm.
1) The analog input is received through a
twisted pair shielded cable. This cable should
be wired separately from power lines or any
other lines which may induce electrical noise.
2) If a voltage ripple occurs during input, or
there is electrically induced noise on the
external wiring, connect a smoothing
capacitor of 0.1 to 0.47µF, 25V.
3) If you are using current input, connect the V+
and I+ terminals to each other.
4) If there is excessive electrical noise, connect
the FG frame ground terminal with the
grounded terminal on the LX3V-4AD.
5) Connect the ground terminal on the
LX3V-4AD unit with the grounded terminal
on the main unit. Use class 3 grounding on
the main unit, if available.