WECO 5K3 LV/HV
41
2.6
Overview of Multi Cluster System
-Double BUS BAR-
ATTENTION:
BOTH ENDS OF THE CLUSTER MUST BE CONNECTED WITH TWO OUTPUT CABLES 50 mm2.
CABLES LENGTH SHALL NOT EXCEED 250cm.
Suggested constant current for a cluster of 8 modules is 350A (18200W) and the suggested output
cable is composed of two sets of 50 mm2 each.
2X 50 mm2 = 2 cables 50 mm2 connected to both poles
(Positive pole has two connection screws, Negative pole has two connection screws)
COPPER BUS BAR
14 Nm (10.33 ft lb)
Terminal Block must be checked every 3 months.
1st
8
th
or Last
2X50/75mm²
2X50/75mm²
Rj45 CAN BMS
Rj45 PARALLEL COM