59
USER MANUAL
–
WebdynSunPM
Version 2.05
préliminaire
o
Parameters
: 1. A wait of 1ms is applied between 2 frames.
o
Category
: Inverter.
o
Model
: WR21TL09
o
DefFIle
: WPM00C715_SMA_Inverter_SMA_WR21TL09.csv. The definition file
name that describes the different variables detected on the SMA-Net device.
•
modbus ethernet
:
o
Index
: 1. Index for the second modbus device configured on the concentrator
o
Interface
: 192.93.121.23:502. This value indicates that the device is of the
Ethernet type at IP address 192.93.121.23 using the default port number, i.e.
502.
o
Name
: ethernet_192.93.121.23_502_126. The name that will be displayed on
the local web pages
o
Address
: 126. This device responds at the modbus 126 address
o
AcqPeriod
: 600. The acquisition period is set to 600 seconds, or one record
every 10 minutes
o
Timeout
: 5000. The timeout is set to 5000ms
o
SerialNumber
: empty. Not applicable
o
Parameters
: 1. The connection is kept alive.
o
Category
: Inverter
o
Model
: Solar_Inverter
o
DefFIle
:
WPM00C715_SunSpec_inverter_SMA_Solar_Inverter_9301_modbusTCP.csv.
The definition file name that describes the different variables configured for
this device detected using SunSpec
When editing this file using Excel, the following display is shown using the CSV format:
index
interface
name
address
acqPeriod(s)
timeout(ms)
serialNumber
Parameters
Category
model
defFile
IO
Io
36000
WebdynSunPM
ioSunPM
WPM00C715_IO.csv
TIC1
600
41676011381
9600
Meter
WPM00C715_TIC_LINKY.csv
0
SERIAL1
Serial1_
52224
0
600
0
2000388220
1
Inverter
WR21TL09
WPM00C715_SMA_Inverter
_SMA_WR21TL09.csv
1
192.93.12
1.23:502
Etherne
t_192.9
3.121.2
3_502_
126
126
600
5000
1
Inverter
Solar_Inverter
WPM00C715_SunSpec_Inve
rter_SMA_Solar_Inverter_9
301_modbusTCP.csv
If the file is modified using “Excel” type spreadsheet software, the format may be
modified and the “;” delimiters replaced by “,”, making it unusable by the
concentrator. Always make sure to indicate the delimiter format when saving.
3.1.2.1.4
“_sci.ini” file
The “_sci.ini” file contains the list of scripts configured on the concentrator.
The file name is defined as follows: Take the device uid as explained previously and suffix
“_sci.ini” to
it. Thus, in the previous example, the generated file name will be
“WPM00BDE4_scl.ini”.
Содержание WebdynSunPM
Страница 1: ...WebdynSunPM Supervision gateway for photovoltaic installations USER MANUAL...
Страница 9: ...9 USER MANUAL WebdynSunPM Version 2 05 pr liminaire 1 Presentation...
Страница 18: ...18 USER MANUAL WebdynSunPM Version 2 05 pr liminaire 2 Installation and Maintenance...
Страница 39: ...39 USER MANUAL WebdynSunPM Version 2 05 pr liminaire 3 Configuration...
Страница 124: ...124 USER MANUAL WebdynSunPM Version 2 05 pr liminaire factory Parameters none...
Страница 125: ...125 USER MANUAL WebdynSunPM Version 2 05 pr liminaire 4 Operation...
Страница 145: ...145 USER MANUAL WebdynSunPM Version 2 05 pr liminaire 5 Update...
Страница 147: ...147 USER MANUAL WebdynSunPM Version 2 05 pr liminaire...
Страница 148: ...148 USER MANUAL WebdynSunPM Version 2 05 pr liminaire 6 Tools diagnostics...
Страница 150: ...150 USER MANUAL WebdynSunPM Version 2 05 pr liminaire 7 Support...
Страница 152: ...152 USER MANUAL WebdynSunPM Version 2 05 pr liminaire 8 FAQ...
Страница 159: ...159 USER MANUAL WebdynSunPM Version 2 05 pr liminaire 9 APPENDICES...