Pump and Fluid Systems
Chapter 2: Storage & Installation
weatherford.com
14
MP-16 2-Piece 5000 psi January 2013
2.1.8
Installation Checklist
Pump Checklist
□
Ensure the location for installation is dry, flat and well-illuminated, and as close to the
fluid source as possible.
□
Check that the pump is level.
□
Ensure the pump rotation is set to drive the top of the crankshaft towards the fluid end.
□
Ensure that the prime mover drives are properly aligned and configured (see 2.1.3: The
Prime Mover)
□
Ensure all guards on the drives are in place and secure.
Suction Checklist
□
Check that any charge pumps used are of suitable size and are configured correctly.
□
Check that the suction stabilizer is installed and inflated correctly.
□
Ensure that the piping is as short as possible and properly supported.
□
Ensure that vents and drain valves are installed at the proper locations and clear for use.
□
Ensure a pressure gauge is installed at the suction point, preferably with a thermometer
and a low-pressure alarm.
□
Check that the suction piping is properly sized and that there are no components that
may choke or disrupt flow (tight elbows, partial valves, metering devices, etc
…)
Discharge Checklist
□
Ensure the discharge piping is properly sized and supported.
□
Ensure the pressure gauge is correctly installed at the pump discharge, along with the
high-low pressure alarm (if used).
□
Install a discharge pulsation dampener as close to fluid end as possible.
□
Ensure the pressure relief valve is installed and set to the appropriate pressure.
□
Ensure the line from the pressure relief valve directs back to a supply tank and not the
pump suction.
□
Ensure the bypass line is properly installed and functioning.
□
Check that the discharge piping is properly sized and that there are no components that
may choke or disrupt flow (tight elbows, partial valves, me
tering devices, etc…)