GRANUDOS S5, control unit

 

 

 

Index: 02 

Date modified: 11/05/2021 

OI No.: BA SW 014-02 Granudos S5-Steuereinheit EN.docx 

Page 15 of 29 

 

Main menu 

 Settings 

 Config. Cl (chlorine dosing performance) (password entry) 

This setting can only be executed by entering the password. 

DS denotes dosing screw 

Here,  the  dosing  components:  dosing  motors,  dosing  screws  that  can  be  used  are 
displayed. The values are preset ex works and are used as the basis for determining the 
defined maximum dosing performance that is shown when the display is switched on. 

 
The maximum permanent dosing performance defined from the config. is shown here. 
To change the desired dosing performance, the cycle time and the chlorine dosing time 
(Menu Settings 

 Dosing performance) can be changed.  

 
 
 
 

 

 

ATTENTION! 
These values may only be changed if the appropriate components have been installed 

in the dosing device. Otherwise, the dosing performance will be displayed incorrectly!  

 

Maximum  achievable  dosing  performance  depending  on  the  dosing  motor’s  rotation  speed  and  the 

diameter of the dosing screw. 

 

Rotation speed of the dosing 
motor 

Diameter of the dosing screw 

maximum dosing performance* - 
default 

12 rpm 

19 mm 

600 g/h  

35 rpm 

19 mm 

1600 g/h 

60 rpm 

19 mm 

2200 g/h 

12 rpm 

26 mm 

1000 g/h 

35 rpm 

26 mm 

3300 g/h 

60 rpm 

26 mm 

4800 g/h 

 

* The specified values are the maximum dosing performance of the GRANUDOS. This represents 50% of 
the permanent dosing performance. These are approximate /- 20% - depending on the condition of 

the granulate and dosing screw.  

 

Main menu 

 Settings 

 Config pH (acid dosing performance) (password entry)   

This Input can only be performed by entering the password. 
The hose length of the 

installed

 peristaltic pump for acid is set here. The values are 

preset ex works and are used as the basis for the dosing performance display. 
 
If an 

external acid pump

 is used, the menu item "External" must be selected and the 

external pump's dosing performance must be entered.  
 

 
The maximum possible dosing performance is displayed here – see below. To change 
the dosing performance, the cycle time and the pH dosing time can be changed (Menu 
Settings 

 Dosing performance). 

If  the  cycle  time  is  changed,  the  chlorine  dosing  performance  and  the  pH  dosing 
performance change 

at an equal ratio

.  

 

 

ATTENTION! 

These configuration values may only be changed if the appropriate components have 
been  installed  in  the  dosing  device.  Otherwise,  the  dosing  performance  will  be 

displayed incorrectly!  

 

 

 

2400 

Содержание GRANUDOS 10-S5

Страница 1: ...llation instructions Control unit Type GRANUDOS S5 without dosing unit GRANUDOS 45 100 S5 GRANUDOS 15 S5 Operating instructions for the dosing unit GRANUDOS 45 100 No BA SW 003 GRANUDOS 15 No BA SW 00...

Страница 2: ...n menu Event log event and data logging 19 7 Maintenance care faults 20 7 1 Device maintenance 20 7 2 Troubleshooting 21 8 Decommissioning Storage Disposal 23 9 Documents 23 9 1 Declaration of conform...

Страница 3: ...DANGER DANGER denotes a safety notice which if disregarded may lead to serious or life threatening injuries or serious material damage CAUTION CAUTION denotes a safety notice which if disregarded may...

Страница 4: ...licable We request a return within 14 days The costs for subsequent damages and for the processing of warranty claims are excluded There are no warranty claims for damages caused by frost water and el...

Страница 5: ...ed 2 2 Safety notices Carefully read and comply with the operating instructions prior to installation maintenance and use of the device Work on the device and changes in the settings may only be carri...

Страница 6: ...OS 45 100 S5 The control unit has the following main functions Chlorine dosing via dosing screw from the drum GR45 100 or the dosing hopper GR10 M GR15 Acid dosing with peristaltic pump directly from...

Страница 7: ...cation plate see OI Dosing unit for Granudos 10 S5 15 S5 No BA SW 002 for Granudos 45 100 S5 No BA SW 003 3 4 Technical data See the dosing unit of the respective dosing device 4 Installation See the...

Страница 8: ...queried in these areas The password consists of four digits and has a factory default setting of 0123 It protects defined menu areas against unauthorised access We recommend that you change this pass...

Страница 9: ...re displayed at the bottom in each case Startup mode If the specified pump pressure or the minimum water level is not reached undercut within 5 seconds after the start of the booster pump or also duri...

Страница 10: ...menu item Reset alarm Touch the Enter key The alarm relay is temporarily deactivated this does not rectify the fault If the fault subsequently recurs or if the fault is not rectified the alarm relay...

Страница 11: ...input signals return back to main menu Main menu Settings Dosing performanceDosing time monitoring dosing process The Dosing performance menu is used to adjust the dosing performance to the expected c...

Страница 12: ...1m h circulation capacity must be possible in indoor pools In outdoor pools a dosing capacity of 10 g m h is required as a possible dosing performance Calculation Thus for an indoor pool with 600 m an...

Страница 13: ...orination Please select a dosing performance that ensures the availability of the desired concentration during the shock chlorination This dosing performance is used when a filter disinfection is requ...

Страница 14: ...hapter 9 4 Tip First note down operation settings in the operation data sheet Main menu Settings Dust extraction optional password entry This process can only be performed by entering the password The...

Страница 15: ...imum dosing performance default 12 rpm 19 mm 600 g h 35 rpm 19 mm 1600 g h 60 rpm 19 mm 2200 g h 12 rpm 26 mm 1000 g h 35 rpm 26 mm 3300 g h 60 rpm 26 mm 4800 g h The specified values are the maximum...

Страница 16: ...fter capturing the input signal the GRANUDOS doses for chlorine or acid using the set performance If the input signal is pending for a longer time than the set cycle duration another dosing is carried...

Страница 17: ...of manual dosing the status line on the start screen changes from Automatic to manual dosing CAUTION In the Manual dosing operation mode the operating personnel should continuously check the water qua...

Страница 18: ...tch open The symbol indicates Switch closed Use the arrow keys to scroll through the pages List of input tests 1 pH ext 24V potential free signal for pH dosing via external control 2 Cl ext 24V potent...

Страница 19: ...tors 1 pH acid dosing 2 Chlorine dosing 3 Knocker 4x active 4 Heating 5 Actuator dust extraction optional 6 flushing valve dust extraction optional 7 Fault indication with relay output 8 pH acid empty...

Страница 20: ...003 Document all work in the maintenance protocol Open and close the housing DANGER Risk of death due to high voltage All electrical work on the device must only be carried out by trained electricians...

Страница 21: ...e switch see OI Dosing unit To start manually acknowledge alarm 6 3 4 Level min ALARM flushing tub The water level in the flushing tub is low more water is suctioned off than runs into the flushing tu...

Страница 22: ...e for chlorine has been exceeded Chlorine dosing has stopped see 6 2 2 Check the function of the dosing Dosing screw blocked or worn Eliminate fault or blockage see also Chapter 7 for the dosing unit...

Страница 23: ...structions for the dosing unit of the respective dosing device for Granudos 10 S5 15 S5 No BA SW 002 for Granudos 45 100 S5 No BA SW 003 9 Documents 9 1 Declaration of conformity The declaration of co...

Страница 24: ...ing diagrams DANGER Risk of death due to high voltage Any work on the device may only be carried out by trained specialists in accordance with the applicable safety regulations Internal fuses may only...

Страница 25: ...GRANUDOS S5 control unit Index 02 Date modified 11 05 2021 OI No BA SW 014 02 Granudos S5 Steuereinheit EN docx Page 25 of 29 Wiring diagram Network board GRANUDOS 10 15...

Страница 26: ...uring operation 1 Chlorine pH dosing performance Date Date Chlorine 15 seconds 1 15 seconds 1 pH acid 8 seconds 1 8 seconds 1 Cycle 30 seconds 30 360 seconds 30 Dosing time limit acid 0 0 100 minutes...

Страница 27: ...limit chlorine 0 0 100 minutes 5 2 Shock chlorination Chlorine dosing perfor mance 50 depending on the technical configura tion 1 Acid dosing performance 50 depending on the technical configura tion...

Страница 28: ...available through your specialist dealer Please always include the exact product designation and the device serial number with you orders The device serial number can be found on the control housing...

Страница 29: ...ng Config pH Configuration pH acid dosing delete log Delete log files Delay Run on time for dust extraction Level max Maximum level alarm in flushing tub Level min Minimum level alarm pH ext 230V exte...

Отзывы: