background image

GRANUDOS S5, control unit

 

 

 

Index: 02 

Date modified: 11/05/2021 

OI No.: BA SW 014-02 Granudos S5-Steuereinheit EN.docx 

Page 10 of 29 

Start screen – Fault indication – Acknowledge alarm  

If a fault occurs, this will be indicated by a 

red display

 and the fault indication in the 

bottom line.  
For a description of the fault indications, 

see

 

Chapter

 

Fehler! Verweisquelle konnte nicht 

gefunden werden.

Fehler! Verweisquelle konnte nicht gefunden werden.

Faults must be pending for 6 seconds before a notification or an alarm is triggered.  
A distinction is made between 

alarms

 (software alarms, e.g., dosing time monitoring, 

monitoring switch) and 

notifications

 (e.g., “Chlorine empty”).  

 

 
 

 

Examples for fault indications / alarm   

 

Dos-limit Cl  = Dosing time limit for chlorine exceeded 

 

pH empty  = pH (= acid canister) empty 

 

Cl empty 

= Chlorine tank empty 

 

fuse F2 

= Fuse F2, for details, see 

Chapter 

Fehler! Verweisquelle konnte nicht gefunden werden.

Fehler! Verweisquelle konnte nicht gefunden werden.

 

 

Notice! 
An alarm will be automatically deleted when its cause has been remedied. For example, 

when the empty chemical container has been exchanged with a full one. 

 

Acknowledge alarm  

 

Use the Enter key to switch to the main menu 

 

Use the arrow keys to navigate to the menu item “Reset alarm”  

 

Touch the Enter key 

 

The alarm relay is temporarily deactivated; this does not rectify the fault! If the fault subsequently recurs, 
or if the fault is not rectified, the alarm relay will be reactivated. 

 

Navigate back to the operation mode; this will restart the device. 

Special cases 

 

The two alarms for the dosing time monitoring 

“Dos-limit” cannot automatically be deleted and must 

always be acknowledged manually

!  

 

In case of the faults 

“pres. min”

 or 

“Level min”

 the 

startup mode

 starts 5 times for 120 seconds each 

to check whether the fault is still pending. (See 6.2.2) 

o

 

If the fault is rectified during the 5 startup attempts, the device returns to the previous state, e.g., 
automatic operation.  

o

 

If the fault still continues after this, the GRANUDOS switches off.    

o

 

If the GRANUDOS has switched off, the fault must be acknowledged manually. To do so, the “Reset 
alarm” command must be carried out twice: Once to reset the alarm, and once to reset the startup 
delay. Now, the GRANUDOS will start up again and the cause of the fault can be investigated.  

 

Settings – see Chapter 6.3.1 

For adapting parameters and system settings: 
Dos perform., Shock chl., System, Dust extraction, Delay b-pump, Config. Cl (= rated dosing performance), 
Config. pH, Control, Teach Cl, Input invers, return 
 

Service – see Chapter 6.3.2 

For input and output test and device information. 

 

Event Log – see Chapter 6.3.3 

Displays the past 25 fault indications 
 

 

 

Содержание GRANUDOS 10-S5

Страница 1: ...llation instructions Control unit Type GRANUDOS S5 without dosing unit GRANUDOS 45 100 S5 GRANUDOS 15 S5 Operating instructions for the dosing unit GRANUDOS 45 100 No BA SW 003 GRANUDOS 15 No BA SW 00...

Страница 2: ...n menu Event log event and data logging 19 7 Maintenance care faults 20 7 1 Device maintenance 20 7 2 Troubleshooting 21 8 Decommissioning Storage Disposal 23 9 Documents 23 9 1 Declaration of conform...

Страница 3: ...DANGER DANGER denotes a safety notice which if disregarded may lead to serious or life threatening injuries or serious material damage CAUTION CAUTION denotes a safety notice which if disregarded may...

Страница 4: ...licable We request a return within 14 days The costs for subsequent damages and for the processing of warranty claims are excluded There are no warranty claims for damages caused by frost water and el...

Страница 5: ...ed 2 2 Safety notices Carefully read and comply with the operating instructions prior to installation maintenance and use of the device Work on the device and changes in the settings may only be carri...

Страница 6: ...OS 45 100 S5 The control unit has the following main functions Chlorine dosing via dosing screw from the drum GR45 100 or the dosing hopper GR10 M GR15 Acid dosing with peristaltic pump directly from...

Страница 7: ...cation plate see OI Dosing unit for Granudos 10 S5 15 S5 No BA SW 002 for Granudos 45 100 S5 No BA SW 003 3 4 Technical data See the dosing unit of the respective dosing device 4 Installation See the...

Страница 8: ...queried in these areas The password consists of four digits and has a factory default setting of 0123 It protects defined menu areas against unauthorised access We recommend that you change this pass...

Страница 9: ...re displayed at the bottom in each case Startup mode If the specified pump pressure or the minimum water level is not reached undercut within 5 seconds after the start of the booster pump or also duri...

Страница 10: ...menu item Reset alarm Touch the Enter key The alarm relay is temporarily deactivated this does not rectify the fault If the fault subsequently recurs or if the fault is not rectified the alarm relay...

Страница 11: ...input signals return back to main menu Main menu Settings Dosing performanceDosing time monitoring dosing process The Dosing performance menu is used to adjust the dosing performance to the expected c...

Страница 12: ...1m h circulation capacity must be possible in indoor pools In outdoor pools a dosing capacity of 10 g m h is required as a possible dosing performance Calculation Thus for an indoor pool with 600 m an...

Страница 13: ...orination Please select a dosing performance that ensures the availability of the desired concentration during the shock chlorination This dosing performance is used when a filter disinfection is requ...

Страница 14: ...hapter 9 4 Tip First note down operation settings in the operation data sheet Main menu Settings Dust extraction optional password entry This process can only be performed by entering the password The...

Страница 15: ...imum dosing performance default 12 rpm 19 mm 600 g h 35 rpm 19 mm 1600 g h 60 rpm 19 mm 2200 g h 12 rpm 26 mm 1000 g h 35 rpm 26 mm 3300 g h 60 rpm 26 mm 4800 g h The specified values are the maximum...

Страница 16: ...fter capturing the input signal the GRANUDOS doses for chlorine or acid using the set performance If the input signal is pending for a longer time than the set cycle duration another dosing is carried...

Страница 17: ...of manual dosing the status line on the start screen changes from Automatic to manual dosing CAUTION In the Manual dosing operation mode the operating personnel should continuously check the water qua...

Страница 18: ...tch open The symbol indicates Switch closed Use the arrow keys to scroll through the pages List of input tests 1 pH ext 24V potential free signal for pH dosing via external control 2 Cl ext 24V potent...

Страница 19: ...tors 1 pH acid dosing 2 Chlorine dosing 3 Knocker 4x active 4 Heating 5 Actuator dust extraction optional 6 flushing valve dust extraction optional 7 Fault indication with relay output 8 pH acid empty...

Страница 20: ...003 Document all work in the maintenance protocol Open and close the housing DANGER Risk of death due to high voltage All electrical work on the device must only be carried out by trained electricians...

Страница 21: ...e switch see OI Dosing unit To start manually acknowledge alarm 6 3 4 Level min ALARM flushing tub The water level in the flushing tub is low more water is suctioned off than runs into the flushing tu...

Страница 22: ...e for chlorine has been exceeded Chlorine dosing has stopped see 6 2 2 Check the function of the dosing Dosing screw blocked or worn Eliminate fault or blockage see also Chapter 7 for the dosing unit...

Страница 23: ...structions for the dosing unit of the respective dosing device for Granudos 10 S5 15 S5 No BA SW 002 for Granudos 45 100 S5 No BA SW 003 9 Documents 9 1 Declaration of conformity The declaration of co...

Страница 24: ...ing diagrams DANGER Risk of death due to high voltage Any work on the device may only be carried out by trained specialists in accordance with the applicable safety regulations Internal fuses may only...

Страница 25: ...GRANUDOS S5 control unit Index 02 Date modified 11 05 2021 OI No BA SW 014 02 Granudos S5 Steuereinheit EN docx Page 25 of 29 Wiring diagram Network board GRANUDOS 10 15...

Страница 26: ...uring operation 1 Chlorine pH dosing performance Date Date Chlorine 15 seconds 1 15 seconds 1 pH acid 8 seconds 1 8 seconds 1 Cycle 30 seconds 30 360 seconds 30 Dosing time limit acid 0 0 100 minutes...

Страница 27: ...limit chlorine 0 0 100 minutes 5 2 Shock chlorination Chlorine dosing perfor mance 50 depending on the technical configura tion 1 Acid dosing performance 50 depending on the technical configura tion...

Страница 28: ...available through your specialist dealer Please always include the exact product designation and the device serial number with you orders The device serial number can be found on the control housing...

Страница 29: ...ng Config pH Configuration pH acid dosing delete log Delete log files Delay Run on time for dust extraction Level max Maximum level alarm in flushing tub Level min Minimum level alarm pH ext 230V exte...

Отзывы: