12
BURNER WILL LIGHT, BUT 12Vdc WAYNE OIL PRIMARY CONTROL GOES INTO LOCKOUT
(CONT)
Procedure
Status
Corrective Actions
6. Check cad cell sighting
for view of flame.
-
De-energize burner.
-
Unplug cad cell and
clean face with soft
cloth. Check cad cell
positioning for view
of flame. Place cad
cell back in socket.
-
Re-energize burner.
Burner locks out.
Go to step 7
Burner keeps running, until “call
for heat” is satisfied.
System is okay.
7. Check Control & Cad
cell.
-
Remove cad cell
wires from
connectors on the oil
primary control and
leave lead wires
unconnected.
-
Energize burner
-
Place jumper across
cad cell terminals
after burner motor
turns on.
Burner doesn’t run.
Replace primary control.
Burner runs.
Control is okay, replace cad cell.