61
Wavin AS+
Technical Manual
Fig. 50: Straight installation with sleeve / socket.
Fig. 51: Straight installation without sleeve / socket.
Fig. 52: 45° angled installation with / without sleeve / socket.
The distance to external, tested systems (inspected and
approved) must be at least 50 mm between partitioned sec-
tions.
If two Wavin BM-R90 feedthroughs are installed next to each
other, the distance between the pipes must be at least 100
mm in the case of special partitioned sections (sloping pipes,
partition via sleeve/socket or for ceiling installations). In the
case of straight pipes without sleeve/ socket in the partition
area, the collar casings can adjoin each other (distance 0 mm).
Note
The presented data, especially recommendations for the pro-
cessing and use of our products are based on our knowledge
and experience. Due to differences in material and working
conditions that are outside the scope of our influence, we
recommend that sufficient internal trials be conducted in
each case to ensure the suitability of our product to the
intended method and processing purposes. No liability will
be accepted either on the basis of these instructions or from
an oral advice, unless we are accused of gross negligence or
deliberate malice.