26

Recall Parameters

Profile  1

Profile  2

Profile  3

Profile  4

Profile  5

Profile  6

C a n c e l

    R e c a l l   F S P - 2 1 1   P a r m s

Press

Select

Press the 

Up/Down  Arrow 

to  Choose a

Specific Profile

High Mode:

Low Mode: 

Time Delay:

Cut Off:

Sensitivity:

Setpoint:

  N E X T                                     S E N D

< 1 0   Vo l t s >

< 1   Vo l t s >

< 3 0   S e c >

< 1   h o u r >

< M a x >

< 4   f c >

        F S P - 2 1 1   S e t t i n g s

Содержание FSIR-100

Страница 1: ...sensors and provides wireless access for setup and parameter changes The FSIR 100 display shows menus and prompts to lead you through each process The navigation pad provides a familiar way to navigate through the customization fields Within a certain mounting height of the sensor the FSIR 100 allows modification of the system without requiring ladders or tools simply with a touch of a few buttons...

Страница 2: ...on between the sensor and the FSIR 100 configuration tool Simple menu screens let you see the current status of the system and make changes It can change sensor parameters such as high low mode sensitivity time delay cut off setpoints and more Range Indoor 1 30 Outdoor 1 15 ...

Страница 3: ...s The battery status displays in the upper right corner of the display Three bars next to BAT indicates a full battery charge A warning appears on the display when the battery level falls below a minimum acceptable level To conserve battery power the FSIR 100 auto matically shuts off 10 minutes after the last key press ...

Страница 4: ...meter settings They are shown in less than greater than symbols value Once active change them using left and right arrow keys In general the up key increments and the down key decrements a value Selections wrap around if you continue to press the key beyond maximum or minimum values Moving away from the value field overwrites the original value The Home button takes you to the main menu The Back b...

Страница 5: ...dow BAT Home Menu The Home or Main menu displays after the powerup process completes It contains information on the battery status and six menu choices Press up down buttons to lo cate the desired function then press Select The following menus are applicable for the FSP 211 ...

Страница 6: ...after the power up process completes It contains information on the battery status and it shows the available sensor options Press the up or down buttons to highlight the desired sensor then press Select F SP 211 BAT Press Select Choose FSP 211 ...

Страница 7: ...select the same display as shown on page 8 such as High Low Mode Time Delay Cut Off Sensitivity Setpoint and Ramp Fade rates Press Select New Se t t ings Cur re n t Se ttings Test M o d e Re ca l l Profile s S e n so r Configura tion F SP 211 ...

Страница 8: ...amps up to the selected HIGH light level default is 10V Range 0 V to 10 V Increments 0 2 V High Mode Low Mode Time Delay Cut Off Sensitivity Setpoint N EXT SEND 10 Volts 1 Volts 5 Min 1 hour Max 4 fc FSP 211 Settings Press the Left Right Arrow to Increase or Decrease Volts ...

Страница 9: ...ected LOW light level default is 1V Low Mode will usually be less than High Mode for proper functioning Range OFF 0 V to 9 8 V Increments 0 2 V High Mode Low Mode Time Delay Cut Off Sensitivity Setpoint NE XT SEND 10 Volts 1 Volts 5 Min 1 hour Max 4 fc F S P 211 Settings Press the Left Right Arrow to Increase or Decrease Volts ...

Страница 10: ...on for the lights to fade to LOW mode default is 5 minutes Range 30 sec and 5 min to 30 min Increments 1 min High Mode Low Mode Time Delay Cut Off Sensitivity Setpoint NEXT SEND 10 Volts 1 Volts 5 Min 1 hour Max 4 fc F S P 211 Settings Press the Left Right Arrow to Raise or Lower Time Delay ...

Страница 11: ...r Range None No cut off lights will stay in low mode 1 min to 59 min 1 hr to 5 hr press and hold should cause to move faster through the increments Increments 1 min or 1 hr High Mode Low Mode Time Delay Cut Off Sensitivity Setpoint NEXT SEND 10 Volts 1 Volts 5 Min 1 hour Max 4 fc FSP 211 Settings Press the Left Right Arrow to Increase or Decrease Cut Off ...

Страница 12: ...f Fix Low Med Max Sequence On Fix Off Fix Low to Max On Fix relay closed occupancy detection disabled Off Fix relay open occupancy detection disabled High Mode Low Mode Time Delay Cut Off Sensitivity Setpoint NEXT SEND 10 Volts 1 Volts 5 Min 1 hour Max 4 fc F S P 211 Settings Press the Left Right Arrow to Increase or Decrease Sensitivity ...

Страница 13: ...hru the increments Sequence Auto None 1 fc to 250 fc None will disable the setpoint feature The Auto option invokes an automatic calibra tion procedure to establish an appropriate setpoint based upon the contribution of the electric light As part of this procedure the High Mode Low Mode Time Delay Cut Off Sensitivity Setpoint NEXT SEND 10 Volts 1 Volts 5 Min 1 hour Max 4 fc F S P 211 Settings Pres...

Страница 14: ...ating in an off state After this process a new setpoint value is automatically calculated Next To view more settings go to NEXT and press the Select button High Mode Low Mode Time Delay Cut Off Sensitivity Setpoint NEXT SEND 10 Volts 1 Volts 30 Sec 1 hour Max 4 fc F S P 211 Settings Choose NEXT to View More Settings ...

Страница 15: ...level to increase from LOW to HIGH default is none lights switch instantly Range None 1 sec to 60 sec Increments 1 sec Ramp Up Fade Down PRIOR SAVE SEND none none FSP 211 Settings Press the Left Right Arrow to Increase or Decrease Sec ...

Страница 16: ...witch instantly Range None 1 sec to 60 sec Increments 1 sec Prior Ramp Up Fade Down P RIOR SAVE SEND none none FSP 211 Settings Press the Left Right Arrow to Increase or Decrease Sec Ramp Up Fade Down PRIOR SAVE SEND 1 sec 1 sec FSP 211 Se ttings Press the Down Arrow to Choose PRIOR Press Select ...

Страница 17: ...Save Ramp Up Fade Down PRIOR SAVE DONE 1 sec 1 sec FSP 211 Settings Press the Down Arrow to Choose SAVE Profile 1 Profile 2 Profile 3 Profile 4 Profile 5 Profile 6 Cancel Save FSP 211 Parms Press Select Press Select Press the Up Down Arrow to Choose Profile Save FSP 211 Parms ...

Страница 18: ...profiles go to SAVE and press the Select button Send To program the FSP 211 with the selected parameters go to SEND and press the Select button The controlled load should cycle on off once the sensor is programmed Ramp Up Fade Down PR IOR SAVE SEND 1 sec 1 sec FSP 211 Settings Press the Down Arrow to Choose SEND ...

Страница 19: ...meters for a specific sensor These are read only parameters Point and Press Select P oin t to desired Occup a ncy Sensor Press Select N ew Set tings C u rren t Settings Te st Mo de R e call Profiles S enso r Configuration F SP 211 Press Select Choose Current Settings ...

Страница 20: ...ss the Select button Light Level 10 Volts 1 Volts 0 5 Min 1 hour Max 4 fc FSP 211 Settings High Mode Low Mode Time Delay Cut Off Sensitivity Set Point NEXT DONE Press Select to View More Settings Ramp Up Fade Down Light Level PRIOR SAVE DONE 1 sec 1 sec 15fc FSP 211 Settings Press the Down Arrow to Choose PRIOR ...

Страница 21: ...tpoint adjustments Save Ramp Up Fade Down Light Level PRIO R SAVE DONE 1 sec 1 sec 15fc FSP 211 Settings Press the Down Arrow to Choose SAVE Profile 1 Profile 2 Profile 3 Profile 4 Profile 5 Profile 6 C ancel Sa ve FSP 211 Parms Press Select Press Select Press the Up Down Arrow to Choose Profile ...

Страница 22: ...rofiles go to Save and press the Select button Done To be able to go to the FSP 211 Home screen go to DONE and press the Select button Ramp Up Fade Down Light Level PR I OR SAVE DONE 1 sec 1 sec 15fc F S P 211 Setti ngs Press the Down Arrow to Choose DONE ...

Страница 23: ...st Mode cancels automatically after 5 minutes Enable Disable New Setti n gs Current Set t i n gs Test M ode Recall Pro fi l es Sensor C on fi gu r at i on FS P 2 11 Press Select Choose Test Mode Enable Disable FSP 211 Test Mode Press Select Press the Left Right Arrow to Enable or Disable Test Mode ...

Страница 24: ...Point and Press Select Poi n t to desired Occupancy Sensor Pres s Select New Settings is selected Press Select N ew Set t ings C urrent Settings Te s t Mode Recal l Profiles Sens or Configuration F SP 211 ...

Страница 25: ...elect the saved parameter profiles This feature is being used when programming multiple FSP 211 s with the same parameters New Set t ings Curren t Settings Tes t Mode R ecal l Profiles Sen s or Configuration FSP 211 Press Select Choose Recall Profiles ...

Страница 26: ...3 Profile 4 Profile 5 Profile 6 Cancel Recall FSP 211 Parms Press Select Press the Up Down Arrow to Choose a Specific Profile High Mode Low Mode Time Delay Cut Off Sensitivity Setpoint NEXT SEND 10 Volts 1 Volts 30 Sec 1 hour Max 4 fc FSP 211 Settings ...

Страница 27: ...Cut Off Sensitivity Setpoint and Ramp Fade rates TROUBLESHOOTING Problem Display does not come on when I press the Power On Button 1 Make sure the batteries are installed correctly 2 Make sure batteries are good Problem No Response Screen appears Point and Press Select No response from device Pres s Select ...

Страница 28: ... is no daylight available may be the only way to communicate with the sensor Problem If the FSIR 100 still cannot get a response from the device 1 Point to the device and try again 2 Make sure you are pointing at the cor rect type of device 3 Make sure the device is within range 4 Make sure the device is not less than 5 away from the sensor 5 Make sure the device you are pointing at is powered 6 M...

Страница 29: ...32 Please Recycle 15537r4 6 2012 2800 De La Cruz Boulevard Santa Clara CA 95050 Technical Support 800 879 8585 www wattstopper com ...

Отзывы: