Section 8: Water Heater and AquaSolve Startup:
L-OMM-0003_A
• 10/8/2021 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
42
of
157
Figure 18
– Gas Train Illustration
NOTE: Optional components may not be shown.
8.6.4 Water Heater Interlocks
As a safety measure for interfacing with an Energy Management System, the Lync Q Water
Heater includes interlocks that connect to remote devices such as draft dampers, gas pressure
gauges, and air proving switches. The labels at the rear of the unit match the terminal block on
the water heater itself.
W A R N I N G !
Turn off all electrical service to the Element when accessing the remote connections and close
and fasten the control cabinet cover before restoring electrical service to them. The remote
connection terminals are High Voltage or may become High Voltage. If the electrical service is
not turned off and these terminals are touched, a dangerous shock could occur, causing personal
injury or death.