Element
Section 8: Water Heater and AquaSolve Startup:
L-OMM-0003_A
• 10/8/2021 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
34
of
157
Section II
–
Element Startup Procedure
Startup of Element essentially consists of two parts: first the water heater (Section 8) and second
the controls system (Section 9.)
In order to prevent potential damage if energizing the unit dry, breakers 3, 5, and 6 are set open
(turned off) during shipment. The water heater does not have a separate breaker and is controlled
by the main power breaker at the rear of the unit. Close (turn on) all breakers once unit is filled
with water.
It is recommended to open (turn off) the same breakers when draining the unit in order to prevent
accidental use in a dry state.
Breaker
Position
Current
Rating
Connection
1
0.5A
Blowdown Valve
2
5A
Cabinet Lights
3
5A
Booster Pump
4
0.5A
DigiTemp Jr
5
2A
Cold UV System
6
2A
Recirc UV System
7
6A
Sanitation Pump
8
2A
I/O Board and Touchscreen
9
1.5A
Diverter Valve
Table 9
– Local Circuit Breaker Directory
Figure 15
–
Location of primary breaker for Element