manualshive.com logo in svg
background image

4          IOM-ACV-113-19_6113-19 2115 

EDP# 1917091 

© 2021 Watts

IOM-ACV-113-19_6113-19 2115 

EDP# 1917091 

© 2021 Watts         5

Setting the Sustaining Control

STEP 7

Setting the Sustaining Control requires lowering the upstream 
pressure to the desired minimum sustained pressure.

STEP 8

Leave the downstream isolation valve full open and close the 
upstream isolation valve until the inlet pressure drops to the 
desired setting.

STEP 9

Adjust the Sustaining Control screw IN, clockwise, until the inlet 
pressure begins to increase (See Figure 3A), or OUT, counter-
clockwise, to decrease (See Figure 3B), stopping at the desired 
pressure.

STEP 10

Allow pressure to stabilize.

STEP 11

Fine-tune the sustaining setting as required as detailed in STEP 8.

STEP 12

Open upstream isolation valve to return to normal operation.

STEP 12

De-energize solenoid to check that the main valve closes.

STEP 13

At valve closure booster pump will stop. Adjust limit switch collar 
to final position to ensure positive actuation of limit switch elec-
trical contact, if necessary, by sliding up/down to location (See 
Figure 4). 

STEP 6

Opening Speed Flow Control Adjustment: The Opening speed 
needle valve restricts flow out of the cover of the main valve. 

If the main valve is opening too slowly turn the adjustment screw 
OUT, counterclockwise, increasing the rate of opening (See Figure 
2B).

If the main valve is opening too quickly, turn the adjustment screw 

IN, clockwise, decreasing the rate of opening (See Figure 2A).

Figure 4 

Limit Switch in Closed Position

Counterclockwise to INCREASE 

the rate of opening

Clockwise to DECREASE 

rate of opening

2A

2B

Figure 2 

Flow Control

Figure 3 

PV20C — Pressure Sustaining Control

Clockwise to increase inlet 

pressure

3A

3B

Counterclockwise to decrease 

inlet pressure

Содержание LFM113-19

Страница 1: ...the Booster Pump Control Valve 3 Maintenance Schedule 6 Trouble Shooting Guide 6 Valve Disassembly Instructions 8 ACV Schematic 11 Local building or plumbing codes may require modifica tions to the information provided You are required to consult the local building and plumbing codes prior to installation If the information provided here is not consistent with local building or plumbing codes the ...

Страница 2: ... Control Valves ACVs are designed for horizontal in line instal lation with the cover facing up main valve stem vertical Slow operation or premature stem and guide wear may occur if valve is not installed according to factory recommendations Consult factory for detailed engineering review prior to ordering if valve is to be installed other than horizontally in line 5 If valve is equipped with a pi...

Страница 3: ...hat the manual operator is turn counter clockwise to a full OUT position See Figure 1 STEP 2 Energize the solenoid to check actuation and to confirm connec tion to power source STEP 3 De energize the solenoid prior to initial pump start STEP 4 Loosen a tube fitting or cover plug at the main valve to allow air to vent during start up STEP 5 Energize the solenoid at pump start to open the main valve...

Страница 4: ...e energize solenoid to check that the main valve closes STEP 13 At valve closure booster pump will stop Adjust limit switch collar to final position to ensure positive actuation of limit switch elec trical contact if necessary by sliding up down to location See Figure 4 STEP 6 Opening Speed Flow Control Adjustment The Opening speed needle valve restricts flow out of the cover of the main valve If ...

Страница 5: ... specification sheets for approximate cover capacity A continuous flow of water from the open port indicates a damaged diaphragm or loose disc diaphragm assembly Disassemble valve and replace diaphragm or tighten disc diaphragm assembly Test 2 Seat Seal Test 1 Close downstream isolation valve and install pressure gauges on an open inlet and outlet port of main valve 2 Open upstream isolation valve...

Страница 6: ...ild or replace Pressure Sustaining Control Main Valve will not close Closed isolation valves in pilot system Check isolation valves ensure open Diaphragm is damaged Conduct diaphragm seal test repair and replace if necessary Main valve stem assembly corroded damaged Inspect stem assembly clean replace if necessary Blockage in main valve Perform freedom of movement test if valve does not close disa...

Страница 7: ...Remove cover nuts and washers 3 Remove the cover If cover is not free to be removed loosen it by tapping upward along its outside edge with a dull cold chisel pic tured above a Large valves may require the installation of lifting eye bolts in order to facilitate cover removal installation ports are provided on the cover for this purpose 4 Remove the Disc and Diaphragm Assembly from the valve body ...

Страница 8: ...brush or by using a Mineral Dissolving Solution Inspect parts for wear and replace if necessary 7 Inspect valve seat If seat is not damaged removal is not necessary Valve seats 6 and smaller are threaded into the body of the valve and require a seat removal tool Figure 5 Table 1 details the tool dimensions for seat removal Valve seats 8 and larger are held in the valve body with stainless steel ca...

Страница 9: ...oth travel by following the Freedom of Movement Test procedure in previous section 11 Test the integrity of the Seat Seal by following the Seat Seal Test procedure in previous section 12 Return valve to service by following instructions on the Technical Bulletin matching the valve function Size in 11 4 11 2 2 21 2 3 4 6 8 10 12 14 16 P N 0677 01 0677 01 0677 02 0677 03 0677 04 0677 05 0677 06 0677...

Страница 10: ...ess Steel 10 Diaphragm Washer ASTM A536 65 45 12 Epoxy Coated Ductile Iron 11 Diaphragm Buna N Nitrile 12 Disc Retainer ASTM A536 65 45 12 Epoxy Coated Ductile Iron 13 Seat Disc Buna N Nitrile 14 Spacer Washer x5 NY300 Fiber 15 Disc Guide ASTM A743 CF8M 316 Stainless Steel 16 Shaft ASTM A276 304 Stainless Steel 17 Seat Ring ASTM A743 CF8M 316 Stainless Steel 17A Seat Screw 8 and Larger ASTM A276 3...

Страница 11: ...IOM ACV 113 19_6113 19 2115 EDP 1917091 2021 Watts 11 NOTES ...

Страница 12: ...not be responsible for any incidental special or consequential damages including without limitation lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly other costs resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other circumstances o...

Отзывы: