background image

  

DET-5-M1 

DET-12-M1  DET-20-M1

   

Order No. 

Order No. 

Order No.

 

Description

 0067700 

0067701 

0067702

  Max. Pressure - psi 

150 

150 

150

  Max. Temp. - °F 

200 

200 

200

  Tank Volume - gal. 

2.1 

4.5 

8.5

  Tank Acceptance - gal. 

.85 

1.8 

3.4

  Air Pre-charge - psi 

20 

20 

20

  Connections Size - in. 

3

4

 male 

3

4

 male 

3

4

 male

  Diameter - in. 

8

1

2

 10 12

1

2

  Length - in. 

11

1

2

 15 19

3

16

  Weight - lbs. 

10 

15

Models: DET-5-M1, DET-12-M1, DET-20-M1

Potable Hot Water Expansion Tank

Installation Instructions

Certified to ANSI/NSF 61

(73°F/23°C) 

Listed by IAPMO

Acceptance Volume

  Air Side 

  Water Side Volume at 150psi

 Pre-pressure 

 

(10.3 bar) (gallons)

 (psi) (bar)  DET-5-M1 

DET-12-M1 

DET-20-M1

 20 

(1.4)

 1.500 

2.801 

7.102

 40 

(2.8)

 1.272 

2.208 

5.882

 60 

(4.1)

 .996 

2.076 

4.705

 80 

(5.5)

 .720 

1.716 

4.009

Figure 1

(Optional Location)

Support Tank 
in Optional 
Horizontal 
Position

(Optional Location)

Watts 
Pressure 
Gauge

Watts 
Backflow Preventer

Water 
Supply

Watts 
Shutoff 
Valve

Watts Pressure
Reducing Valve

Expansion
Tank

Water

Heater

To System

Watts
T&P
Safety
Relief
Valve

Floor Drain

Discharge Line

IS-DET-M1

 

!

 

W A R N I N G !

Improper installation, adjustment, alteration, service or maintenance can cause property dam-
age, serious bodily injury or death. Read instructions completely before proceeding with instal-
lation. Only qualified personnel may install or service this equipment in accordance with local 
codes and ordinances.

Do not exceed 80psi (5.5 bar) air charge. Air charge pressure exceeding 80psi (5.5 bar) could 
become hazardous and will void any and all warranties, either written or implied. Failure to fol-
low these instructions will result in the possibility of property damage, serious bodily injury
or death.

This Expansion Tank is designed and intended for water storage at a maximum pressure of 
150psi (10.3 bar) and a maximum temperature of 200°F (93ºC). Any use other than for potable 
water or a sustained or instantaneous pressure in excess of 150psi (10.3 bar) or 200°F (93ºC)
is 

UNSAFE

 and can cause property damage, serious bodily injury or result in death.

Disclaimer:

 The manufacturer of this tank does not accept any liability or other responsibility for 

personal injury or property damage resulting from improper use, installation or operation of this tank
or the system of which it is a part.

Notice:

 The expansion tank, piping and your connections may in time leak. Select a location

to install the expansion tank where a water leak will not damage the surrounding area. The manu-
facturer is not responsible for any water damage in connection with this expansion tank.