manualshive.com logo in svg
background image

 

3

 

ES-A-ACV-LF985GD  2115 

© 2021 Watts

Threaded = 400psi (27.6 bar)
150# Flanged = 250psi (17.2 bar)
300# Flanged = 400psi (27.6 bar) 
Grooved End = 400psi (27.6 bar)

Operating Pressure

1

3

4

2(L)

CLOSES VALVE

OPENS VALVE

FLOW

5

X

X

X/Y

(Supply Pressure)

Globe Flanged

Angle Flanged 

Globe Threaded

Globe Grooved End

Angle Threaded

Angle Grooved End

Basic Valve Body Options 

Standard Materials

Body and Cover:

        Ductile Iron ASTM A536

Coating:

  

      NSF Listed Fusion Bonded Epoxy  

 

 

   Lined 

and 

Coated

Trim:

  

      316 Stainless Steel

Elastomers:

   

      Buna-N (standard) 

 

   EPDM 

(optional) 

 

   Viton™ 

(optional)

Nut, Spring and Stem:

   Stainless Steel

Anti-Scale (Optional):

     Xylan Coated Stem and Seat

Viton™ is a trademark of The Chemours Company FC, LLC

M Series Basic Valves

Deep Well Pump Control Valve

Full Port Ductile Iron Dual Chamber Basic Valve

ACV Schematic - Series LF985GD 

This Ames ACV is a full port, dual chamber basic valve that 

incorporates a one-piece disc and diaphragm assembly. This 

assembly is the only moving part within the valve, allowing it to 

open or close as commanded by the pilot control system. 
When pressure is applied to the upper diaphragm chamber and 

released from the lower diaphragm chamber, the valve travels 

to a closed position. When pressure is applied to the lower 

diaphragm chamber and released from the upper diaphragm 

chamber the valve travels to a full open position. When pressure 

is balanced between the upper and lower diaphragm chambers, 

the valve will hold an intermediate position until commanded to 

modulate open or closed by the pilot control system.
Ames ACV Main Valves are Lead Free. The Ames ACV piloting 

system contains Lead Free* components, ensuring all of our con-

figurations are Lead Free compliant.
Globe Pattern Dual Chamber Basic Valve (

900GD) 

Angle Pattern Dual Chamber Basic Valve (

900AD)

Operating Temperature

Buna-N: 160°F (71°C) Maximum
EPDM: 300°F (140°C) Maximum
Viton™: 250°F (121°C) Maximum
Epoxy Coating**: 225°F (107°C) Maximum

** Valves can be provided without internal epoxy coating consult factory  

Содержание AMES LF985GD Series

Страница 1: ...al codes and ordinances WARNING Need for Periodic Inspection Maintenance This product must be tested periodically in compliance with local codes but at least once per year or more as service condition...

Страница 2: ...e pump starts and stops against an open valve Pump start up When the pump is signaled to start the 4 Way Solenoid is energized and directs fluid and pressure into the cover chamber above the diaphragm...

Страница 3: ...ly This assembly is the only moving part within the valve allowing it to open or close as commanded by the pilot control system When pressure is applied to the upper diaphragm chamber and released fro...

Страница 4: ...ure Drop psi 2 3 4 6 8 10 20 30 40 60 80 100 Flow Rate Gallons per minute Water 2 4 10 20 40 60 80 100 200 500 1000 2000 5000 10000 20000 100000 8 6 1 4 1 6 1 2 1 0 8 6 4 3 2 1 2 2 1 2 1 0 8 6 4 3 2 1...

Страница 5: ...e Iron 11 Diaphragm Buna N Nitrile 12 Inner Bearing Bolts 3 and Smaller ASTM A276 304 Stainless Steel 13 Inner Bearing Retainer 3 and Smaller ASTM A276 302 Stainless Steel 13A Bearing Retaining Ring 4...

Страница 6: ...nter Angle Thread Angle 150 Angle 300 Angle Thread Angle 150 Angle 300 Port Size NPT Port Size NPT Port Size NPT Shipping Weights A B C D E F G H I J K L M in in mm in mm in mm in mm in mm in mm in mm...

Страница 7: ...EPDM optional Viton optional Voltage 24VDC 24VAC or 120VAC Enclosure General Purpose NEMA 4 standard Explosion Proof NEMA 6 6P 7 9 optional Action 4 Way Actuation Solenoid Action only Main valve actio...

Страница 8: ...the valve opens or closes The adjustable collar is normally set to contact the trip arm when the main valve is closed The collar can be positioned on the stem by loosening the set screw to actuate the...

Страница 9: ...n In the free flow direction the seat moves out of the flow path to all unrestricted flow Specifications Standard Flow Control Large Flow Control FLOW FLOW CLOSED Fluid Speed Controlled by Needle FLOW...

Страница 10: ...ilot circuit speed controls and pilots The filter element can be accessed for cleaning by removing the clean out cap or may be cleaned by installing an optional blow down ball valve The wetted surface...

Страница 11: ...re used in pilot lines to provide a positive shutoff in any override or maintenance situation for simple trouble shooting This 2 piece full port valve features bottom loaded stems PTFE seats and packi...

Страница 12: ...switches at the desired point of valve travel Body Material Stainless Steel Elastomers Buna N standard EPDM optional Viton optional Enclosure NEMA 1 3 4 and 13 General Purpose standard NEMA 1 7 and 9...

Страница 13: ...made during installation to protect the piping circuit from dam age Only remove the pilot control system from the valve if necessary Tubing and fittings should be kept clean and replaced exactly as re...

Страница 14: ...of movement and remove excess air trapped within the cover chambers See Figure 1 Below To increase the rate of opening closing turn the adjustment screws on the speed controls OUT counterclockwise In...

Страница 15: ...e flow goes into the lower chamber the Opening speed flow control restricts flow out of the upper cham ber of the main valve If valve opening is too slow turn the adjustment screw OUT counterclockwise...

Страница 16: ...valve specification sheets for approximate cover capacity A continuous flow of water from the open port indicates a damaged diaphragm or loose disc diaphragm assembly Disassemble valve and replace di...

Страница 17: ...ation valves ensure open Diaphragm is damaged Conduct diaphragm seal test repair and replace if necessary Main valve stem assembly corroded damaged Inspect stem assembly clean replace if necessary Blo...

Страница 18: ...em Nut examine stem threads for mineral build up Remove deposits with a fine wire brush Extreme care should be taken not to damage the finish on stem guiding surfaces when disassembling Avoid applying...

Страница 19: ...s not work properly other costs resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other circumstances ove...

Отзывы: