Modulex EXT Commercial Series
CHAPTER 8: Maintenance Schedule
OMM-0160_A
• DRAFT Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
82
of
117
6.5.2 Manual Setpoint Function
1. Click on the Manual Setpoint button
icon. This will show an Activate Button.
2. Toggling the Activate button allows user to operate the boiler with a manual setpoint. Any
setpoint in the Heating or DHW Mode are ignored while the Manual Setpoint Function is
activated.
3. Click on the R/- buttons to set the manual setpoint desired.
4. To disable the Manual Setpoint Function, click on the Home button
.