Edge [ii] Controller Operation Manual
SECTION 4: DIAGNOSTICS
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
82
of
196
4. To run a pre-defined sequence, press the
Profile
parameter and select
Profile 1
, then
enable the
Profile Run
control. This profile exercises the Blower in increments from 0 to
10 volts then back to 0.
5. Using either method,
Blower
(voltage) and
Blower
(rpm) are displayed continuously.
4.4.3 Ignition
Complete the instructions below to test the ignition system. Note, the Safety Shutoff Valve does
not open during this test.
1. Go to:
Main Menu
→
Diagnostics
→
Subsystems
→
Ignition
.
Figure 4.4.3-1: Subsystems: Ignition Screen
2. Start the
Ignition Spark
test or
Flame Scanner Relay
test (available only on
Benchmark 5000 & 6000) by enabling its control.
3. The Igniter Solenoid opens the gas assist line solenoid and generates sparking of the igniter
until the
Ignition Spark
control is disabled.
4. Enabling the
Flame Scanner Relay
enables the relay.
5. In both tests, the
Spark Current
is displayed continuously during the test.
Figure 4.4.3-2: Subsystems: Ignition Screen