Edge [ii] Controller Operation Manual
SECTION 2: EZ SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
31
of
196
2.3.2 EZ Setup: BST Manager Unit
The Manager unit will sync with all Client boilers once this process is completed. Note, if a BST
Manager setup was already performed on this or another unit, and you want to load/re-load that
setup, see
NOTE:
All “Client” units are typically setup before starting the BST Manager setup, so their addresses
are available during this process. If they are
not
all setup, you will have to pause and setup all
Client units before completing the BST Manager setup.
1. Go to:
Main Menu
→
EZ Setup
.
2. If the unit was previously setup, the
EZ Setup
screen appears showing a summary of the
previous setup (see Figure 2.3.1-1, above). You can
Abort
and retain the previous setup or
press
Next
to continue.
3. On the
Select Configuration
screen press
BST Cascade
, then press
Next
.
Figure 2.3.2-2: BST Manager: Select Configuration Screen
4. On the
Cascade Role
screen select
BST
Manager
and then press
Next
. The Manager LED
will light on the front panel signifying the role of the unit.
Figure 2.3.2-3: BST Manager: Cascade Role Screen