Edge [ii] Controller Operation Manual
SECTION 6
– ADVANCED SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
112
of
196
5. Go to:
Main Menu
→
Advanced Setup
→
Access
and enter your password.
6. Go to:
Main Menu
→
Advanced Setup
→
Unit
→
Firmware Update
.
7. Press the
Download Latest Version
button. The firmware is copied from the Internet
directly to the USB device installed in Step 2. This may take a minute or more. With the
Intelligent BootLoader installed, this step also downloads updated graphics and/or I/O Board
files, plus additional files, if there are any.
8. The Progress is displayed as the files are downloaded. Once completed, the screen
displays
Downloads Complete
. If an error message is displayed, repeat the previous step,
or complete the instructions in the previous section to download the file(s) to a USB device
plugged into an external computer.
Figure 6.2.7.3-2: Firmware Update Screen
NOTE:
The download only needs to be performed once on a single USB device. That device can then
be used to update all boilers and/or all water heaters.
Updating the Controller’s Firmware
Complete the instructions below to update the firmware from the USB device used above.
1. Verify that the USB device containing the latest firmware is plugged into the Controll
er’s
USB port.
2. Verify that the
Enable/Disable
switch on the Controller’s front face is set to
Disable
.
3. Go to:
Main Menu
→
Advanced Setup
→
Unit
→
Firmware Update
(enter your password
if prompted; this screen requires a password). Note, the controls are disabled (greyed out)
until the USB device is installed
and
the
Enable/Disable
switch is in the
Disable
position.
4. Press the
Update Main Control
button (see Figure 6.2.7.3-2, above).
5. When done, the
Update Finished
screen appears displaying the new version number and
the current date.
Do not remove the USB device until this screen appears
. Verify that the
expected version and date is displayed. If so, press
OK
to continue.