SECTION 2: INSTALLATION
•
•
•
Connector Strip J6 Terminals
Pin # Name
Description
1
Remote Interlock Out
Connection to an auxiliary device interlock - requires delay before firing.
2
Remote Interlock Return
3
Delayed Interlock 1 Out
Connection to an auxiliary device interlock - requires delay before firing.
4
Delayed Interlock 1 Return
5
(NOT USED)
6
(NOT USED)
Connector Strip J7 Terminals
Pin # Name
Description
1
Spare 2 Relay N.O.
Connection to an auxiliary device enable/disable signal, such as:
•
System Pump •
Pump 2 •
Louver
•
Louver 2 •
Damper •
Other
To assign/program its function, go to the Controller’s
Main Menu
→
Advanced Setup
→
Ancillary Devices
→
Relays
,
then set the
Relay
to
Spare 2 Relay
and the
Name
to one of the above devices.
2
Spare 2 Relay Com
3
DHW Pump Relay N.O.
Connection to a DHW Pump enable/disable signal.
4
DHW Pump Relay Com
5
V2/Spare 1 Relay N.O.
Connection to an auxiliary device enable/disable signal, such as:
•
System Pump •
Pump 2 •
Louver
•
Louver 2 •
Damper •
Other
To assign/program its function, go to the Controller’s
Main Menu
→
Advanced Setup
→
Ancillary Devices
→
Relays
,
then set the
Relay
to
V2/Spare 1 Relay
and the
Name
to one of the above devices.
6
V2/Spare 1 Relay Com
7
Reserve Relay N.O.
Connection to a reserve/backup boiler enable/disable signal.
8
Reserve Relay Com
9
(NOT USED)
10
(NOT USED)
11
Fault Relay N.O.
Connection to a Fault/Remote Alarm enable/disable signal.
12
Fault Relay Com
13
Aux Relay N.O.
Connection to an auxiliary device enable/disable signal.
14
Aux Relay Com
Connector Strip J14 Terminals
Pin # Name
Description
1
BAS RS485 +
Connection to the building automation system (BAS) network (Modbus RTU, BACnet
MSTP). For IP network, use the Ethernet port.
2
BAS RS485 -
3
(NOT USED)
4
(NOT USED)
5
(NOT USED)