Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 5
– SAFETY DEVICE TESTING
OMM-0145_A99
• GF-218 • 9/18/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
87
of
157
5.6.2
Delayed Interlock Test
Delayed Interlock Test Instructions
1.
Remove the cover from the I/O Box and locate the DELAYED INTL’K IN terminals.
2. On the Controller, go to:
Main Menu
→
Diagnostics
→
Manual Mode
, then enable the
Manual Run
control.
3. Set the valve position between 25% and 30% using the
+
(Plus) and
–
(Minus) controls.
4. If there is a jumper across the
DELAYED INTL’K IN terminals, remove one side of the
jumper. If the interlock is connected to a proving switch of an external device, disconnect
one of the wires leading to the proving switch.
5. The unit should shut down and display a
Delayed Interlock Open
fault message. The
FAULT
LED should be flashing.
6. Reconnect the wire or jumper removed in step 5 to restore the interlock.
7. Press the
CLEAR
button to reset the fault
8. The unit should start.