Benchmark Platinum-Edge [ii]: Operation-Service Manual
SECTION 4
– INITIAL START-UP
OMM-0137_J
• 12/20/2022 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
48
of
167
4.5.2 PROPANE Gas Combustion Calibration
These instructions apply only to units running
PROPANE
gas.
PROPANE Combustion Calibration Instructions
1.
Set the Edge Controller’s Enable/Disable switch to
Disable
.
2. Open the water supply and return valves to the unit and ensure that the system pumps are
running.
3. Open the
PROPANE
supply valve to the unit.
4. Turn external AC power to the unit
ON
.
5. On the Controller, go to:
Main Menu
→
Calibration
→
Manual Combustion
. If necessary,
enter a technician level password.
6. The first
Manual Combustion Calibration
screen appears. Complete the three steps
listed before continuing with the instructions.
In addition
, if your unit is running AERtrim,
you must turn that feature off before continuing, as AERtrim will interfere with combustion
calibration.
Figure 4-7: First Manual Combustion Calibration Screen
7. Connect the gas pressure manometer to the
upstream
side of the gas train’s SSOV, as
shown in Section 4.2.2 and connect the Combustion Analyzer and Multimeter, as shown in
Section 4.2.3, and ensure that the heating loop is capable of dissipating sufficient heat at
full fire.
8. Verify that the incoming gas pressure to the unit is within the allowable range (see the
Benchmark Gas Supply Guide
(TAG-0047, GF-2030)).
9. Once you have completed the previous step, move the manometer (or use a secondary
one) to the
downstream
side of the SSOV and press
Next
to continue.
10. For the NOx requirement choose
None
.
Figure 4-8: Choose NOx Requirement