Benchmark Platinum-Edge [ii]: Operation-Service Manual
SECTION 10
– TROUBLESHOOTING
OMM-0137_J
• 12/20/2022 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
130
of
167
SECTION 10:
TROUBLESHOOTING
10.1 INTRODUCTION
This section is intended to aid service/maintenance personnel in isolating the cause of a fault in your
Benchmark boiler. The troubleshooting procedures below are presented in tabular form on the
following pages. These tables are comprised of three columns labeled: Fault Indication, Probable
Cause and Corrective Action. The numbered items in the Probable Cause and Corrective Action
columns correspond to each other. For example, Probable Cause No. 1 corresponds to Corrective
Action No. 1, etc.
NOTE:
All AERtrim troubleshooting messages are included in Section 9.6, above.
When a fault occurs in the unit, proceed as follows to isolate and correct the fault:
Fault Correction Instructions
1. Observe the fault messages displayed on the Edge Controller.
2. Refer to the Fault Indication column in Troubleshooting Table 10-1, below, and locate the Fault that
best describes the existing conditions.
3. Proceed to the Probable Cause column and start with the first item (1) listed for the Fault Indication.
4. Perform the checks and procedures listed in the Corrective Action column for the first Probable
Cause candidate.
5. Continue checking each additional Probable Cause for the existing fault until the fault is corrected.
6. Section 10-2 contains additional troubleshooting information that may apply to situations in which no
fault message is displayed.
If the fault cannot be corrected using the information provided in the Troubleshooting Tables, contact
your local AERCO Representative.