5.9.2 Bypass Flow Piping Method
A bypass flow system is recommended under one or more of the following conditions:
•
If the total system flow is
greater
than the amount required by the indirect heat exchanger.
•
If pool or spa water system exceeds 95°F in temperature, a bypass flow configuration is
used to cool down the return flow in order to prevent tripping the high limit switch and to
prevent water with temperatures over 115°F from entering the pool or spa system.
•
Multiple unit installations.
An example of the configuration and necessary components for a
bypass flow
system are shown
in Figure 5-5b.
Figure 5-5b: Bypass Flow Piping Method
FILTER
PUMP
FLOW SWITCH
HEAT
EXCHANGER
BOILER
HIGH TEMP.
SWITCH
CHLORINATOR
(DOWNSTREAM)
TO POOL
FROM
POOL /
SKIMMER
BYPASS PIPING