Specifications 

n

Accritem Controller

Model 3

Technical Instructions

IS-P-TC744-1

Operation

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Direct or Reverse Acting

Adjustment Dial Range—Standard 50 to 350°F (10 to 177°C)
Maximum Supply Pressure (air or water) 

 

at Room Temperature

  . . . . . . . . . . . . . . . . . . . . . . . . . .

35 psi (241.3 kPa)

Air Consumption (max.)

. . . . . . . . . . . . . . . . . . . . . . . . .

218 cm 3/s (800 SCIM)

Maximum Operating Pressure

  . . . . . . . . . . . . . . . . . . . . . .

1724 kPa (250 psi)

Maximum Operating Temperature

  . . . . . . . . . . . . . . . . . . . . . . . .

400°F(204°C)

Temperature Response

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

0.5°F(0.3°C ) 

Mounting

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1/2" NPT

Air or Water Connections

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1/8" NPT

Drain Connection (water only)

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1/4" NPT

Shipping Weight

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4 lbs. (1.8 kg)

Sensitivity (adjustable)

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1 to 27.9 kPa/C

 

 

(1/4 to 2-1/4 psi/F)

Maximum Pressure on Wells 

 

Stainless Steel no. 744-082

  . . . . . . . . . . . . . . . . . .

 1125 psi (7756 kPa) 

 

Copper no. 744-111

  . . . . . . . . . . . . . . . . . . . . . . . . . . . .

 525 psi (3619 kPa)

Well Dimensions

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

See page 6

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use infor-

mation can result in death, serious personal injury, 

property damage, or damage to the equipment.
Keep this Manual for future reference.

AiR OpERAtEd: 

Rigid Stainless Bulb

  

Direct Action  

744-1270

  Reverse Action   744-1271

Rigid Copper Bulb

  

Direct Action  

744-1213

  Reverse Action   744-1214

WAtER OpERAtEd:

Rigid Stainless Bulb

  Direct Action  

744-1217

  Reverse Action   744-1218

You are required to consult the local building and plumbing 

codes prior to installation.  If the information in this manual is 

not consistent with local building or plumbing codes, the local 

codes should be followed. Inquire with governing authorities for 

additional local requirements.

WARNING

!

WARNING

!

Flush all pipes thoroughly before installation. Installation and  

field adjustment are the responsibility of the installer. 

WARNING

!

Need for periodic inspection and Yearly Maintenance: 

  

Periodic inspection and yearly maintenance by a licensed con-

tractor is required. Corrosive water conditions and/or unauthor-

ized adjustments or repair could render the valve ineffective for 

service intended. Regular checking and cleaning of the valve’s 

internal components and check stops helps assure maximum 

life and proper product function. Frequency of cleaning and 

inspection depends upon local water conditions.

FAiLURE tO COMpLY WitH pROpER iNStALLAtiON ANd 

MAiNtENANCE iNStRUCtiONS COULd CONtRiBUtE tO tHE 

VALVE FAiLURE.
this Hot Water Master tempering Valves cannot be used for 

tempering water temperature at fixtures. Severe bodily injury 

(i.e., scalding or chilling) and/or death may result depending 

upon system water pressure changes and/or supply water 

temperature changes. ASSE standard 1016, 1069 or 1070 listed 

devices should be used at fixtures to prevent possible injury.

These Hot Water Tempering Valves are designed to be 

installed at or near the boiler or water heater. They are not 

designed to compensate for system pressure fluctuations and 

should not be used where ASSE standard 1016, 1069 or 1070 

devices are required. These valves should never be used to 

provide “anti-scald” or “anti-chill” service.
The components of the system must be of materials with a 

construction capable of withstanding the high limit output tem-

peratures of the water heating source.

WARNING

!

Содержание POWERS Accritem Controller 3

Страница 1: ...uthorities for additional local requirements WARNING WARNING Flush all pipes thoroughly before installation Installation and field adjustment are the responsibility of the installer WARNING Need for P...

Страница 2: ...nse time Also see Figure 8 on page 7 Figure 1 Operation Instructions n 2 The sensitivity of the Accritem controller is adjusted by turn ing the restriction screw Figure 2 The restriction screw is fact...

Страница 3: ...Both Air and Water Controllers To disassemble Refer to Parts Drawing and Figure 5 1 Remove knob 3 after loosening its set screw 2 Remove cover plate 2 3 Remove spring retainer screw 8 and lever sprin...

Страница 4: ...ighten the knob set screw very firmly 8 Turn the adjusting knob to the desired control temperature for approximate calibration 9 Recalibrate as required after the controller is installed and connected...

Страница 5: ...1 Stainless Steel 10 Cover Screw 030 041 030 041 6 Brass 11 O Ring Not used 047 050 1 Silicone Rubber 12 Retaining Ring 100 124 100 124 1 Phos Bronze 13 Valve 744 155 744 163 1 Phos Bronze 15 Valve Sp...

Страница 6: ...744 107 Dotted line item not included Provides materials necessary to reduce the incoming air supply pressure to within the supply pressure range of the Accritem WATER Accessory Kit No 744 180 Dotted...

Страница 7: ...e Normally CLOSED valve Hot piped to Normally OPEN port of valve Valve OPENS on air failure Valve CLOSES on air failure Valve opens to HOT flow on air failure REVERSE Acting Normally CLOSED valve Norm...

Страница 8: ...on This expresswarranty is in lieu of and excludes all otherwarranties guarantees or representations express of implied There are no impliedwarranties oF merchantability or of fitness for a particular...

Отзывы: