![WattNode WNC-3Y-208-MB Скачать руководство пользователя страница 56](http://html1.mh-extra.com/html/wattnode/wnc-3y-208-mb/wnc-3y-208-mb_installation-and-operation-manual_3751197056.webp)
56 Specifications
Specifications
Models
Model
Nominal Vac
Line-to-Neutral
Nominal Vac
Line-to-Line
Phases
Wires
WNC-3Y-208-MB
120
208–240
3
4
WNC-3Y-400-MB
230
400
3
4
WNC-3Y-480-MB
277
480
3
4
WNC-3Y-600-MB
347
600
3
4
WNC-3D-240-MB
120*
208–240
3
3–4
WNC-3D-400-MB
230*
400
3
3–4
WNC-3D-480-MB
277*
480
3
3–4
*Note: the delta models have an optional neutral connection that may be used for measuring
wye circuits. Delta models use the phase A and phase B connections for power.
Table 12: WattNode Models
Model Options
Any of these models are available with the following options. See the CCS website
page for details.
General Options
:
Pre-assign xxx as the global
CtAmps
value of the attached current
transformers.
:
Pre-assign xxx to
CtAmpsA
, yyy to
CtAmpsB
, and zzz to
CtAmpsC
.
This is used if non-matching CTs are connected to different phases.
Communication Options
:
Factory configure the Modbus RS-485 communications to even parity (E81).
Parity:
even
Data bits:
8
Stop bits:
1
:
Factory configure the RS-485 communications 19,200 baud. Position 8 of the DIP
switch will be ignored.
:
Factory configure the RS-485 communications to 38,400 baud. Position 8 of the
DIP switch will be ignored.
Configure the communications to the Modbus TCP-RTU protocol option for
use with RS-485 to Ethernet gateways (serial device adapters).
Factory configure the Modbus address. The DIP switch address will be ignored.
X Terminal Options
These options all utilize the
X
(auxiliary) terminal on the
MODBUS
connector:
Provides 5 Vdc at up to 60 milliamps between the
C
(common) and
X
(5V) terminals.
Output Voltage:
5 Vdc ± 5%
Minimum Output Current:
0 mA
Maximum Output Current:
60 mA
Maximum Short-Circuit Output Current:
150 mA
Recommended Maximum 5V Wire Length:
30 cm (1 foot)