TROUBLESHOOTING

CAUTION

TURN POWER OFF AT THE CIRCUIT BREAKER 

BEFORE WORKING WITH OR NEAR HIGH VOLTAGE.

For any unexpected operation

1.  Check DIP switch settings.

2.  Make sure the switches are set according to the defi ned settings in the DIP 

Switch Setting chart.

Lights do not turn on with occupancy, and the LED does not fl ash: 

1.  DIP switch #6 must be ON to enable the LED.

2.  Check that the circuit breaker has been turned back on.

3.  The Ultrasonic Sensitivity setting may need to be increased. 

Turn clockwise as needed.

4.  Check all sensor and power pack wire connections.

5.    Check for 24V input to the sensor. 

If 24V is present, replace the sensor.

 If 24V is not present, check that high voltage is present to power pack. 
If it is, replace power pack.

Lights do not turn off automatically:

1.   The sensor may be experiencing activations from outside the controlled area or 

from some type of interference (see “Unwanted Sensor Activations” below).

2.  Check all sensor wire connections.

3.   Disconnect power pack’s blue wire:

If the lights do not turn off, replace power pack. Reconnect blue wire.
If the lights turn off, the problem may be in the sensor–to check:

 

Reconnect the blue wire.
 Turn sensitivity and time delay to minimum and allow the sensor to time out. 
If the lights turn off, the sensor is working properly (see number 1, above, and 
“Sensor Adjustment” for readjustment of sensor). 

4.   Set sensitivity and time delay to minimum and allow the sensor to time out. 

If the lights turn off, the sensor is working properly (see number 1, above, and 
“Sensor Adjustment” for readjustment of sensor). 

Visit our website for FAQs: www.wattstopper.com

Содержание UT-300-1

Страница 1: ...lay Rating 1A 30VDC VAC Operating Temperature 32 to 131 F 0 to 55 C Time Delay Adjustment 5 to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 5 sec upon intial power up or DIP switch reset Ultrasonic Coverage Model UT 300 1 up to 500 ft 2 Model UT 300 2 up to 1000 ft 2 Model UT 300 3 up to 2000 ft 2 Sensitivity Adjustment Minimum to Maximum trimpot Frequency 40kHz Ins...

Страница 2: ... an occupancy detection The UT 300 operates on 24V supplied by Watt Stopper Power Packs The sensors can operate on 24VDC 24VAC or half wave rectified AC UT 300 sensors also have an isolated relay with Normally Open and Normally Closed contacts for interfacing with HVAC or EMS systems COVERAGE PATTERN The UT 300 is available in 3 models Each model has a different size coverage pattern The coverage s...

Страница 3: ...s Mount the sensor to the ceiling The UT 300 is designed for a ceiling height of about 8 10 feet Mounting above or below this range will significantly affect the coverage patterns As a general rule each occupant should be able to clearly view the sensor Open Office Area Coverage To get complete coverage in an open office area install multiple sensors so that there is approximately 20 overlap with eac...

Страница 4: ...re from one side of switch to Common terminal on sensor Wire from other side of switch to Man Switch terminal on sensor Wiring the ISOLATED RELAY The Isolated Relay is rated for 1A 30VAC VDC Connect the wires necessary to the application that requires this output Relay Common must be used for proper operation N O Normally Open Closed when occupancy is detected N C Normally Closed Open when occupan...

Страница 5: ...ng Spring Clips 2 Blue Control Out 24V Common Low Voltage Class 2 Line Voltage Line Neutral Feed Through Power Pack Black Red 1 2 Line Voltage Switches Visit our website for FAQs www wattstopper com White Black Red Line Voltage Wire Color Legend Standard wiring with local off switch ...

Страница 6: ...ck 24V Low Voltage Class 2 Line Voltage Line Neutral Feed Through Power Pack Man Switch Red UT 300 Common For low voltage momentary switch set UT 300 DIP switch 1 ON Man Switch Common Jumper Back of LVS 1 White Black Red Line Voltage Wire Color Legend Manual On wiring with low voltage momentary switch ...

Страница 7: ... the front cover onto the sensor Using an Octagonal J Box 1 Pull the low voltage wires from the power pack into the J Box through the conduit knockout 2 Connect the low voltage wires to the appropriate terminals on the sensor 3 Loosen the appliance mounting screws attached to the J Box 4 Align the sensor in the J Box so that the mounting screws on the box match the key holes on the sensor s rear h...

Страница 8: ...4 Remain still The LED should not flash The lights should turn off after 5 seconds If not see Troubleshooting 5 Move about the coverage area The lights should come on Adjust the Ultrasonic Sensitivity as necessary to provide the desired coverage Green LED indicates activation from the ultrasonic sensor When testing and adjustment is complete reset DIP Switches to the desired settings and replace th...

Страница 9: ...A manual switch provides the following additional functionality a The load can be turned ON by manual switch activation and it stays on as long as occupancy is detected The sensor time delay operates as programmed When the load turns OFF due to lack of occupancy detection the load can be turned ON again by occupancy detection or switch activation b Activating the manual switch while the load is ON...

Страница 10: ... of the time delay the sensor will turn the lights off The sensor can select the time delay using SmartSet or you can select a fixed time delay SmartSet records occupancy patterns and uses this history to choose an optimal time delay from 5 to 30 minutes SmartSet behavior starts immediately and is refined continually as history is collected Walk through mode turns the lights off three minutes after ...

Страница 11: ...wer pack If it is replace power pack Lights do not turn off automatically 1 The sensor may be experiencing activations from outside the controlled area or from some type of interference see Unwanted Sensor Activations below 2 Check all sensor wire connections 3 Disconnect power pack s blue wire If the lights do not turn off replace power pack Reconnect blue wire If the lights turn off the problem ...

Страница 12: ...p to 1000 sq ft coverage Low Voltage w Isolated Relay and Manual On feature UT 300 3 Ultrasonic Occupancy Sensor up to 2000 sq ft coverage Low Voltage w Isolated Relay and Manual On feature UT 305 1 2 3 Ultrasonic Occupancy Sensor Low Voltage BZ 50 Power Pack 120 230 277VAC 50 60Hz 225mA 20A ballast or incandescent 1HP 120 250VAC BZ 150 Power Pack 120 230 277VAC 50 60Hz 225mA 20A ballast or incand...

Страница 13: ...he part of The Watt Stopper Inc for consequential damages arising out of or in connection with the use or performance of this product or other indirect damages with respect to loss of property revenue or profit or cost of removal installation or reinstallation 2800 De La Cruz Boulevard Santa Clara CA 95050 Technical Support 800 879 8585 www wattstopper com 03630r2 10 2008 Please Recycle ...

Отзывы: