
Presentation Mode
is a feature of the Auto ON mode. When both relays are
manually turned OFF the PW holds the lights OFF until no motion has been
detected for the duration of the Time Delay. With subsequent occupancy, the PW
turns the load ON. If both relays are ON and one relay is manually turned OFF
this relay remains OFF until both the Time Delay and retrigger delay expires for
the relay that is ON, after that time the ON Mode control settings again apply.
INSTALLATION
1. Make sure that the power has been turned OFF at the circuit breaker.
2. Connect wires to the PW flying leads as shown in the
wiring diagram.
The ground wire (green) must be
fastened to ground for the sensor to work properly.
3. Attach the sensor to the wall box by inserting screws into
the two wide holes on the top and bottom of the attached
metal bracket. Match them up with the holes in the wall
box and tighten.
4. Turn the circuit breaker ON. Wait one minute, then push the Auto ON/OFF
switch for each load and the lights will turn ON. There is a delay due to initial
power-up of the sensor that only occurs during installation.
5. Test and adjust the sensor if necessary.
6. Attach the cover plate.
#12 – #14 AWG
Cu Wire Only
Strip Gage
1/2"
12.7mm
Visit our website for FAQs: www.wattstopper.com
WARNING
TURN THE POWER OFF AT THE CIRCUIT BREAKER
BEFORE INSTALLING THE SENSOR OR WORKING ON THE LOAD.
Ground
PW-203
PW-203
Junction Box
Junction Box
Black (Line)
Red (Load 1)
Brown (Load 2)
Blue (Line)
White (Neutral)
Yellow (Traveler)
Load 1
Load 2
1
2
120-277V 50/60Hz
White (Neutral)
Black (Line)
PW-203 Wiring
Important:
Wire the remote unit to the same branch circuit as the main unit
controlling the load. If relay 2 of the main unit cannot be controlled from the
remote unit, check wiring to be sure both units are on the same branch circuit.
Caution:
Do not install this device if there is not at least 10 meters (30 feet) or
more of wire between the unit and the electrical service panel.