Watt Stopper PW-203 Скачать руководство пользователя страница 5

Auto ON 

DIP 8

 

OFF 

for Relay 1

DIP 9

**

 OFF 

for Relay 2

Alerts

The PW can provide audible and/or visible alerts as a warning before the load 
turns OFF.

Turning ON Loads (ON Mode)

The relays are programmed independently for either Auto ON or Manual ON. In 
either mode, the load can be turned ON or OFF using the ON/OFF button.

Unit will beep at one minute*, at 30 seconds and at 10 
seconds before turning OFF load. When Walk-Through 
is active, the unit beeps three times at 10 seconds 
before the load goes OFF. 
*If Visible Alert is also ON, the one-minute time-out 
warning beep is replaced by the visible alert.

Audible 
Alerts

(DIP 7 ON)

When only one minute is left in the time delay, the load 
connected to the relay turns OFF for one second. This 
provides a one minute warning before the load(s) are 
turned OFF by the sensor.

Visible Alert

(DIP #6 ON)

No Visible Alerts 

(DIP 6 OFF)

No visible warnings provided.

No audible warnings provided.

No Audible Alerts

(DIP 7 OFF)

With an ON Mode DIP switch in the OFF position, the load turns 
ON and OFF automatically based on occupancy. If the load is 
turned OFF manually, Presentation Mode operation applies. This 
prevents the load from turning ON automatically after it was 
deliberately turned OFF. Pressing the button to turn lights ON 
returns the sensor to Auto ON mode. 

**

  Switch 9 default is ON for Manual ON functionality of Relay 2 to comply with 

California Energy Commission Title 24 bi-level switching requirements.

Manual ON

DIP 8

 

ON 

for Relay 1

DIP 9

**

 ON 

for Relay 2

With an ON Mode DIP switch in the ON position, the occupant 
must press the ON/OFF button to turn ON the load. The sensor 
keeps the load ON until no motion is detected for the selected 
time delay. There is a 30 second re-retrigger delay. If occupancy 
is detected during the delay, the sensor turns the load back ON. 
After the re-trigger delay elapses the ON/OFF button must be 
pressed to turn ON the load.

Call 800.879.8585 for Technical Support

 

  

Relay 

Default ON Mode 

DIP switch # 

Setting

 PW-203 

Auto ON 

OFF

  

Manual ON 

ON

Содержание PW-203

Страница 1: ...c or electronic ballast Horsepower Rating each relay 1 6 HP 120VAC Time Delay Adjustment 5 to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 5 sec for 10 min with DIP switch setting PIR Adjustment High or Low DIP switch Light Level Adjustment 8fc to 180 fc Alerts Selectable Audible Visual Cover plate not included US Patents 5640113 6617560 PW 203 Passive Infrared Mult...

Страница 2: ...ccupancy turns ON all the lights that are connected to the same circuit The occupant can turn OFF the load at any time by pressing the ON OFF button of any sensor that is connected to the circuit If the occupant forgets to turn OFF the lights the last sensor to detect occupancy turns them all OFF after the time delay expires A walk through mode can turn lights OFF after only 3 minutes if no activi...

Страница 3: ...egree field of view The red LED on the sensor flashes when the PIR detects motion Masking the lens Opaque adhesive tape is supplied so that sections of the PIR sensor s view can be masked This allows you to eliminate coverage in unwanted areas Since masking removes bands of coverage remember to take this into account when troubleshooting coverage problems PIR Coverage 7 5 2 2m 15 4 5m 20 6 1m 35 10 ...

Страница 4: ...e first 30 seconds If motion continues beyond the first 30 seconds the set time delay applies High DIP 5 OFF Default setting Suitable for most applications PIR Sensitivity Adjustment The PW sensor constantly monitors the controlled environment and automatically adjusts the PIR to avoid common ambient conditions that can cause false detections while providing maximum coverage Reduces sensitivity by...

Страница 5: ...ings provided No Audible Alerts DIP 7 OFF With an ON Mode DIP switch in the OFF position the load turns ON and OFF automatically based on occupancy If the load is turned OFF manually Presentation Mode operation applies This prevents the load from turning ON automatically after it was deliberately turned OFF Pressing the button to turn lights ON returns the sensor to Auto ON mode Switch 9 default i...

Страница 6: ...ll box and tighten 4 Turn the circuit breaker ON Wait one minute then push the Auto ON OFF switch for each load and the lights will turn ON There is a delay due to initial power up of the sensor that only occurs during installation 5 Test and adjust the sensor if necessary 6 Attach the cover plate 12 14 AWG Cu Wire Only Strip Gage 1 2 12 7mm Visit our website for FAQs www wattstopper com WARNING T...

Страница 7: ...e aid of artificial light In order to set this as the threshold level of brightness so that the artificial lights remain OFF perform the following steps 1 Make sure the room is lit appropriately 2 Put the sensor into TEST mode using the Time Delay DIP switches 3 Press and hold the ON OFF button Relay 1 button on the PW 203 for 3 seconds until you hear a beep 4 Step away from the sensor After 25 se...

Страница 8: ... 7 Disabled Enabled Audible Alert 4 Disabled Enabled Walk Through 9 1 2 3 4 5 6 7 8 Time Delay Walk Through ON Relay 1 Mode Relay 2 Mode Audible Alerts PIR Sensitivity Visible Alerts Test 10 minutes 15 minutes 20 minutes 25 minutes 30 minutes Service 5 minutes 1 2 3 Time Delay Service bypasses occupancy light level functions Control the load manually using ON OFF button 6 Disabled Enabled Visible ...

Страница 9: ...t turn ON call 800 879 8585 for technical support Lights do not turn OFF 1 There can be up to a 30 minute time delay after the last motion is detected To verify proper operation set DIP switch 1 to ON then reset switches 1 2 and 3 to OFF to start Test Mode Move out of view of the sensor The lights should turn OFF in approximately 5 seconds 2 Verify that the sensor is mounted at least six feet 2 me...

Страница 10: ...t damages with respect to loss of property revenue or profit or cost of removal installation or reinstallation 2800 De La Cruz Boulevard Santa Clara CA 95050 Technical Support 800 879 8585 www wattstopper com 10188r2 9 2010 Please Recycle COVER PLATES WattStopper PW series wall switches fit behind industry standard decorator style switch cover plates Units come in the following colors which are in...

Отзывы: