Watt Stopper DSW-301 Скачать руководство пользователя страница 2

Alerts

The DSW can provide audible alerts as a warning before the load turns OFF.

High 

(DIP #4 OFF)

Default setting. Suitable for most applications.

PIR Sensitivity Adjustment

The DSW sensor constantly monitors the controlled environment and 

automatically adjusts the PIR to avoid common ambient conditions that can 

cause false detections, while providing maximum coverage. 

Time Delay 

(15 min. 

DIP 1 ON & 2 OFF)

Time delays of 5, 

15

 (default), or 30 minutes are 

available. See DIP SWITCH SETTINGS for information.

Test/20 min  

(DIP 1 & 2 OFF)

A Test Mode with a short time delay of five seconds 

is set when DIP switches 1 & 2 are OFF. It cancels 

automatically after ten minutes, or when you set a 

fixed time delay. When the Test Mode times out, the 

sensor will assume a 20 minute time delay. To restart 

Test Mode, change the time delay setting to any fixed 

amount and then return it to the Test setting.

Reduces sensitivity by approximately 50%. Useful in 

cases where the PIR is detecting movement outside of 

the desired area (also consider masking the lens) and 

where heat sources cause unnecessary activation.

Low, 50%

(DIP #4 ON)

Unit will beep at one minute, at 30 seconds and at 10 

seconds before turning OFF load. When Walk-Through 

is active, the unit beeps three times at 10 seconds 

before the load goes OFF. 

Audible Alerts

(DIP #7 ON)

No Alerts

No warnings provided.

Walk-Through

The Walk-Through mode shortens the time delay to reduce the amount of time 

the load is ON after a brief moment of occupancy, such as returning to an office 

to pick up a forgotten item then immediately exiting.

Walk-Through 

Mode

(DIP #3 ON)

The DSW sensor turns the load OFF 3 minutes after 

the area is initially occupied, if no motion is detected 

after the first 30 seconds. If motion continues beyond 

the first 30 seconds, the set time delay applies.

No Walk-Through

Walk-Through mode disabled.

Shading indicates default operation. 

Time Delays

The DSW sensor holds the load ON until no motion is detected for the selected 

time delay. Select the time delay using DIP switch settings. In the DSW-302, 

both relays use the same delay.

Содержание DSW-301

Страница 1: ...1200W ballast E ballast LED 1 6 HP 347VAC 1500W ballast LED 1 6 HP Time Delay Adjustment 5 to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 10 min with 5 sec time delay...

Страница 2: ...where the PIR is detecting movement outside of the desired area also consider masking the lens and where heat sources cause unnecessary activation Low 50 DIP 4 ON Unit will beep at one minute at 30 se...

Страница 3: ...setting table in order to deem the area occupied Both requires motion detection by the PIR and the Ultrasonic Either requires motion detection by only one technology PIR requires motion detection by...

Страница 4: ...utton for each load and the lights will turn ON There is a delay due to initialpower up of the sensor that only occurs during installation 5 Test and adjust the sensor INSTALLATION DSW 302 and DSW 302...

Страница 5: ...on all models Sensors can easily be wired together for convenient control of a common load When wiring this way only use 300 series sensors Multi Way in 300 series is not compatible with prior sensor...

Страница 6: ...er delay for the sensor set in Manual ON mode or instant re trigger for the sensor set in Auto ON mode After the re trigger delay elapses the ON OFF button of the sensor set in Manual ON mode must be...

Страница 7: ...se wiring Black Black Neutral Neutral optional Line Yellow Red Primary Load Brown Secondary Load Neutral optional Ground Green Green Ground Green Green Red Brown Blue Blue Black Black Neutral Ground G...

Страница 8: ...button The DSW 302 contains two relays and two ON OFF buttons to allow control of one or two loads independently Pressing a button toggles the state of the corresponding relay Optional Neutral is als...

Страница 9: ...minutes Test 20 min 15 minutes 30 minutes Time Delay 5 6 Trigger Mode Initial Occupancy Maintain Occupancy Re trigger seconds duration Option C Both Both Both 5 Standard Either 5 Either Option A Eithe...

Страница 10: ...e button assembly Gently pull it away from the unit When the adjustments are completed replace the button cap by inserting its hinges into the tabs on the main unit and then squeeze the top of the but...

Страница 11: ...ion Verify that there is no significant heat source e g high wattage light bulb mounted near the sensor 3 Verify that the trimpot is not pointing at Service red LED ON If so rotate the trimpot to it s...

Страница 12: ...s in materials and workmanship for a period of five 5 years There are no obligations or liabilities on the part of WattStopper for consequential damages arising out of or in connection with the use or...

Отзывы: