Service Mode

To override all sensor functions, set DIP switch 6 to the OFF position. The red 

LED will come on and stay on for the duration of the override.

TROUBLESHOOTING

CAUTION

USE PROPER SAFETY PRECAUTIONS 

WHEN WORKING WITH OR NEAR 

HIGH VOLTAGE

Lights will not turn on:

1.  Verify the lens is not masked in the direction being tested (see Masking).
2.  Adjust Sensitivity settings up if needed (DIP switches #7 & 8).
3.  Verify power pack and sensor connections are correct and secure.
4.  Check for +24VDC at RED wire from the power pack to sensor.

•  If present, the problem may be with the sensor. Try another sensor 

(if available).

•  If there is no voltage, see Power Pack High Voltage Checklist, below.

Lights will not turn off:

1.  Check that Time Delay settings are correct (DIP switches #1 – 6).
2.  Decrease Sensitivity settings if needed (DIP switches #7 & 8).
3.  Verify power pack and sensor connections are correct and secure.
4.  Disconnect BLUE wire on power pack from sensor.

•  If the lights turn off, the problem may be in the sensor. Turn 

Sensitivity and Time Delay to minimum and allow the sensor to 

time-out.

•  If the lights turn off, the sensor is working correctly. See Unwanted 

Sensor Activations, next page. And go through the Sensor Adjustment 

process again.

•  If the lights stay on, the problem may be in the power pack. See 

Power Pack High Voltage Checklist, below.

Isolated relay not functioning properly:

CAUTION: Use proper high voltage precautions, if applicable.

1.  Check that Time Delay settings are correct (DIP switches #1 – 6).
2.  Check Sensitivity setting. Also see, Unwanted Sensor Activations, next 

page.

3.  Verify all wire connections from sensor are correct and secure.
4.  Check that there is voltage to the Isolated Relay.
5.  Check for +24VDC at RED wire from the power pack to sensor.
6.  Use an ohmmeter to check the function of the Isolated Relay:

•  Turn off the power connected to Isolated Relay wires (if applicable). 
•  With motion in front of the sensor’s lens, check that the 

connection between the BROWN and RED wires is open.

•  With motion in front of the sensor’s lens, check that the 

connection between the ORANGE and RED wires is closed.

Check Our Web Site For FAQs: www.wattstopper.com

Содержание CI-200

Страница 1: ...emperature 32 to 131 F 0 to 55 C Time Delay Adjustment 15 seconds 30 minutes PIR Coverage Model CI 200 up to 1200ft2 Model CI 200 1 up to 500ft2 Light Level Adjustment 1 190FC Sensitivity Adjustment M...

Страница 2: ...overage Patterns The CI 200 has a multi cell multi tier Fresnel lens with a field of view of 360 The sensor has two lens pattern options The Extended Range Lens will cover up to 1200 sq ft when mounte...

Страница 3: ...more than 12 14ft you may start to significantly reduce sensitivity Often the best location to install a CI 200 in a closed office is off center see fig 1 Avoid placing a sensor directly in line with...

Страница 4: ...ation of coverage in unwanted areas The mask is cut as needed and mounted onto anchor pins in the sensor s cover IMPORTANT Do not use the mask if full coverage is desired IMPORTANT Before securing the...

Страница 5: ...a second load for occupancy and light level ambient light control connect BLUE wire from power pack to yellow wire on sensor BLUE wire from slave pack to blue wire on sensor BLACK wire from slave pack...

Страница 6: ...nal adjustment leave the setting at maximum The controlled lights will then not be affected by ambient light levels To make the light level adjustment The final light level setting for normal operatio...

Страница 7: ...problem may be in the sensor Turn Sensitivity and Time Delay to minimum and allow the sensor to time out If the lights turn off the sensor is working correctly See Unwanted Sensor Activations next pag...

Страница 8: ...cy Sensor with High Density Reduced Range Lens BZ 50 Power Pack 120 277VAC 50 60Hz 20A ballast or incandescent B347D P Power Pack 347VAC 60Hz 150mA 15A ballast S120 277 347E P Slave Pack 120 277VAC 60...

Отзывы: