Calibration Manual

Registered Company

 

Winona, Minnesota  USA

 

ISO 9001

97

TOTAL

3 Year Warranty

CUS

CUSTTO

OM

MER

ER

SSA

ATISF

TISFA

ACTI

CTIO

ON

N

Series 96

1/16 DIN Temperature Controller

with Custom Toolbar 

(patent pending)

Watlow Controls

1241 Bundy Blvd., P.O. Box 5580, Winona, Minnesota USA 55987-5580

Phone: (507) 454-5300, Fax: (507) 452-4507  http://www.watlow.com

Содержание Series 96

Страница 1: ...ISO 9001 97 TOTAL 3Y earWarranty CUS CUST TO OM MER ER S SA ATISF TISFA ACTI CTIO ON N Series 96 1 16 DIN Temperature Controller with Custom Toolbar patent pending Watlow Controls 1241 Bundy Blvd P O Box 5580 Winona Minnesota USA 55987 5580 Phone 507 454 5300 Fax 507 452 4507 http www watlow com ...

Страница 2: ...stent with your application inputs outputs alarms limits etc If the problem persists after checking the above you can get technical assistance from your local Watlow representative or by dialing 507 454 5300 ext 1111 An applications engineer will discuss your application with you Please have the following information available when calling Complete model number All configuration information User s...

Страница 3: ...ation 50mV tc00 Thermocouple Calibration 0mV tc32 Thermocouple Calibration 32mV gnd Set Ground LEAd Lead Resistance Calibration r 15 RTD Calibration 15Ω r380 RTD Calibration 380Ω A 0u Process Calibration 1 0V A10u Process Calibration 1 10V A 4A Process Calibration 1 4mA A20A Process Calibration 1 20mA Fcty Factory Page b 0u Process Calibration 2 0V b10u Process Calibration 2 10V b4A Process Calibr...

Страница 4: ...llow 10 seconds for the controller to stabilize Set Thermocouple Calibration 32 tc32 Calibration 1 Menu to yES Press the Advance Key to store type J thermocouple calibration and move to the next prompt 6 Rewire for operation and verify calibration RTD Input Procedure Equipment Required 1kΩ decade box with 0 01Ω resolution Input 1 Setup and Calibration 1 Connect the correct power supply to terminal...

Страница 5: ...n 2 Menu to yES Press the Advance Key to store the 10 00V input and move to the next prompt 8 Rewire for operation and verify calibration Current Process Input Procedure Equipment Precision current source 0 to 20mA range with 0 01mA resolution Input 1 and 2 Setup and Calibration 1 Connect the correct power supply to terminals 8 and 9 see Series 96 User s Manual Input 1 2 Connect the current source...

Страница 6: ...tabilize within one second Repeat until the voltmeter reads 10 00V 0 1V Press the Advance Key to store the value and move to the next prompt 8 Rewire for operation and verify calibration Output 2 Setup and Calibration 1 Connect the correct power supply to terminals 8 and 9 see Series 96 User s Manual Milliamperes 2 Connect the volt ammeter set to milliamperes to terminals 17 and 18 3 At Output Cal...

Страница 7: ...he unit should stabilize within one second Repeat until the ammeter reads 20 00mA 0 1mA Press the Advance Key to store the value and move to the next prompt Volts 5 Connect the volt ammeter set to volts to terminals 19 and 20 6 At Output Calibration 4 1V 4 1 Process Output Calibration Menu enter the reading from the voltmeter The unit should stabilize within one second Repeat until the voltmeter r...

Страница 8: ...n Lock Lock out Menu is not set to hide 1603 w no 0 no no 0 yes yes 3 tc32 Thermocouple Cal ibration 32º Store 32º F type J calibration Active if Calibration Lock Lock out Menu is not set to hide 1603 w no 0 no no 0 yes yes 2 tc50 Thermocouple Cal ibration 50mV Store 50 000mV cali bration for input 1 thermocouple Active if Calibration Lock Lock out Menu is not set to hide 1603 w no 0 no no 0 yes y...

Страница 9: ... 1608 w no 0 no no 0 yes yes 1 b 0u Process Calibra tion 2 0V Store 0 000V calibra tion for input 2 pro cess cin2 Calibration 2 Menu Fcty Factory Page Active if Calibration Lock Lock out Menu is not set to hide 1603 w no 0 no no 0 yes yes 11 A20A Process Calibra tion 1 20mA Store 20 000mA cali bration for input 1 process Active if Calibration Lock Lock out Menu is not set to hide 1603 w no 0 no no...

Страница 10: ...ock Lockout Menu is not set to hide 1609 w 4 00 400 0 00 to 99 99 2 4 Output Calibra tion 2 4mA Enter the output value in milliamps as measured Active if output 1 is process 96 _ _ F _ _ _ _ _ _ _ and Calibra tion Lock Lockout Menu is not set to hide 1607 w 10 00 1000 0 00 to 99 99 1 10 Output Calibra tion 1 10V Enter the output value in volts as measured Active if output 1 is process 96 _ _ F _ _...

Страница 11: ...lude software power supply input 2 four outputs and display color Power Supply A 100 240Vı ac dc B 24 28Vı ac dc Input 2 0 None 1 Event input 0 5VÎ dc 4 20mA remote set point input Output 1 C Switched dc open collector D Electromechanical relay Form C 2A without RC suppression F Universal Process range selectable 0 20mA 4 20mA 0 5VÎ dc 1 5VÎ dc 0 10VÎ dc K 0 5A solid state relay without RC suppres...

Страница 12: ...anted to be free of defects in material and workmanship for 36 months after delivery to the first purchaser for use providing that the units have not been misapplied Since Watlow has no control over their use and sometimes misuse we cannot guarantee against failure Watlow s obligations hereunder at Watlow s option are limited to replacement repair or refund of purchase price and parts which upon e...