Version 1.0
PN: 2042-8198
Page 39 of 75
DN: 10-32813
You may also disable the Watbus discovery feature. Software tools use this feature to discover Watbus
devices on an Ethernet network. By disabling this discovery feature, you must specify the IP address or
host name to make a connection with PC software. See key
Modbus® TCP Server
The RMA PLUS provides up to three (priority based) Modbus® TCP sessions. Unlike Watbus, Modbus®
TCP does not proxy requests. It interacts asynchronously with a user-defined data model loaded on
initialization and configured by way of a USBD gateway file. Because of this, there is virtually no delay
between request and response.
The keep-alive feature is enabled on all accepted sockets. This prevents socket leaks if a socket is not
closed properly. Typical causes include application hang / crash, loss of link, severed network, half close,
etc.
The RMA PLUS is a Modbus® TCP server and only implements the following Modbus® function codes:
•
3: Read Holding Registers
•
4: Read Input Registers
•
6: Write Single Register
•
16: Write Multiple Registers
Modbus® TCP supports all integer data types, floats, enums, and Watbus Parameter types. Strings are
not implemented. See
for more information.
This service is enabled by default for all model numbers. It
may be disabled by writing “No”
to the
Modbus TCP Enable member. NOTE: A reset is required for this change to take effect.
The 16-bit word / register order of multi-register data types may be changed to suit the client
application. By default, the word order is low, high.
Ethernet 70 (0x46), Instance 2
Member ID
Member Name
Data Type
Access
NV
Min
Max
Default
Comments / Description
3
0x03
Modbus TCP Enable
ENUM16
RW
F
106
59: No
106: Yes
4
0x04
Modbus TCP Word Order
ENUM16
RW
F
1331
1331: Low High
1330: High Low
The object model for the Modbus® TCP server is user-defined. A sample file (shown below) exists in the
path defined by the key
. Add records to this file as necessary keeping the following in mind:
•
The Modbus® register is user-defined. It is an unsigned 16-bit integer with a range of 0
–
65535.
•
Records must be sorted in ascending order by Modbus® register (Column A).
•
The file may contain a maximum of 2000 valid records.
•
There is currently a maximum of 500 unique data points per Watbus bus and zone.
•
You must respect the data type of the target element, i.e. 32-bit integers, floats and parameters
consume 2 registers, so you must skip a register number before starting the next custom data point.
Содержание RMA PLUS RMAP-2A Series
Страница 1: ...Version 1 0 PN 2042 8198 Page 1 of 75 DN 10 32813 RMA PLUS User Manual...
Страница 8: ...Version 1 0 PN 2042 8198 Page 8 of 75 DN 10 32813...
Страница 11: ...Version 1 0 PN 2042 8198 Page 11 of 75 DN 10 32813 Figure 3 Ground Wire Location...
Страница 24: ...Version 1 0 PN 2042 8198 Page 24 of 75 DN 10 32813 Figure 20 RMA PLUS via USBD Eject start selected drive...
Страница 26: ...Version 1 0 PN 2042 8198 Page 26 of 75 DN 10 32813 Figure 22 RMA PLUS via USBD MICRO SD root...
Страница 27: ...Version 1 0 PN 2042 8198 Page 27 of 75 DN 10 32813 Figure 23 RMA PLUS via USBD NOR FLASH root...
Страница 29: ...Version 1 0 PN 2042 8198 Page 29 of 75 DN 10 32813 Figure 25 RMA PLUS via USBD Eject stop selected drive...
Страница 42: ...Version 1 0 PN 2042 8198 Page 42 of 75 DN 10 32813 Figure 37 Default web page Index html...
Страница 75: ...Version 1 0 PN 2042 8198 Page 75 of 75 DN 10 32813...