D8 Series User’s Guide
Chapter 6: Menu and Parameter Reference
126
Table 6.15
– Values for Alarm Hysteresis
INPUT TYPE
DISPLAY FORMAT
VALUES
VALUES VIA
COMMUNICATIONS
DEFAULT
Thermocouple
n/a
0 to 500
0 to 5000
2
RTD
n/a
0 to 500.0
0 to 5000
2.0
Proess
-999 to 3000
0 to 500
0 to 5000
2
-9999 to 30000
0 to 5000
0 to 5000
20
-999.9 to 3000.0
0.0 to 500.0
0 to 5000
2.0
-99.99 to 300.00
0.00 to 50.00
0 to 5000
0.20
-9.999 to 30.000
0.000 to 5.000
0 to 5000
0.020
-0.9999 to 3.0000
0.0000 to 0.5000
0 to 5000
0.0020
Alarm Delay
l
01 Alarm delay
r
b
0 sec
Use this parameter to delay a failed sensor, process and deviation alarms until the alarm condition
has been continuously present for longer than the delay time.
To delay alarms on powerup only, see Power Up Alarm Delay on page 103.
Values:
0 to 255 seconds.
Default:
0
DeviceNet™ Object:
Alarm (67 hex)
Process Variable Retransmit Menu
l
01 PV retrans
r
Other menus
b
Use the
PV retrans
menu to configure an output so that it will retransmit the process variable from
another loop. For details, see Setting Up Process Variable Retransmit on page 77.
This menu contains parameters for both heat and cool outputs. The sample screens in this section
show the heat parameters, but the descriptions apply to both the heat and cool parameters.