CLS200 Series User’s Guide
Chapter 2: Installation
43
Table 2.9
—
TB50 Connections for Sixteen-Loop Controllers
TERMINAL
FUNCTION
CONTROL
OUTPUT
1
TERMINAL
FUNCTION
CONTROL
OUTPUT
1
1
+5VDC
2
+5VDC
3
CTRL COM
4
CTRL COM
5
Not Used
6
Watchdog
Timer
7
Pulse Input
8
Global Alarm
9
Output 1
Loop 1 heat
10
Output 34
2
Pulse loop cool
11
Output 2
Loop 2 heat
12
Output 33
Loop 16 cool
13
Output 3
Loop 3 heat
14
Output 32
Loop 15 cool
15
Output 4
Loop 4 heat
16
Output 31
Loop 14 cool
17
Output 5
Loop 5 heat
18
Output 30
Loop 13 cool
19
Output 6
Loop 6 heat
20
Output 29
Loop 12 cool
21
Output 7
Loop 7 heat
22
Output 28
Loop 11 cool
23
Output 8
Loop 8 heat
24
Output 27
Loop 10 cool
25
Output 9
Loop 9 heat
26
Output 26
Loop 9 cool
27
Output 10
Loop 10 heat
28
Output 25
Loop 8 cool
29
Output 11
Loop 11 heat
30
Output 24
Loop 7 cool
31
Output 12
Loop 12 heat
32
Output 23
Loop 6 cool
33
Output 13
loop 13 heat
34
Output 22
Loop 5 cool
35
Output 14
Loop 14 heat
36
Output 21
Loop 4 cool
37
Output 15
Loop 15 heat
38
Output 20
Loop 3 cool
39
Output 16
Loop 16 heat
40
Output 19
Loop 2 cool
41
Output 17
Pulse loop heat
42
Output 18
Loop 1 cool
43
Input 1
44
Input 2
45
Input 3
46
Input 4
47
Input 5
48
Input 6
49
Input 7
50
Input 8
1
The indicated outputs are dedicated for control when enabled in the loop setup. If one or both of a loop’s outputs are
disabled, the corresponding digital outputs become available for alarms or ramp/soak events.
2
For Watlow Serial DAC, the controller uses digital output 34 (terminal 10) for a clock line. You cannot use output 34 for
anything else when you have a control output configured or the SDAC.