CLS200 Series User’s Guide
Chapter 2: Installation
41
External
Switching
Device
TB50
Input
Control Com
Figure 2.24
— Wiring Digital Inputs
TB18 Connections
Table 2.7
—
TB18 Connections
TERMINAL
FUNCTION
CONTROL OUTPUT
1
FOUR-LOOP
CONTROLLER
EIGHT-LOOP
CONTROLLER
1
+5VDC
2
CTRL COM
3
Watchdog timer
4
Global alarm
5
Output 1
Loop 1 heat
Loop 1 heat
6
Output 2
Loop 2 heat
Loop 2 heat
7
Output 3
Loop 3 heat
Loop 3 heat
8
Output 4
Loop 4 heat
Loop 4 heat
9
Output 5
Pulse loop heat
Loop 5 heat
10
Output 6
Loop 1 cool
Loop 6 heat
11
Output 7
Loop 2 cool
Loop 7 heat
12
Output 8
Loop 3 cool
Loop 8 heat
13
Output 9
Loop 4 cool
Pulse loop heat
14
Output 10
Pulse loop cool
Loop 1 cool
15
Output 34
2
Serial DAC clock
Serial DAC clock
16
Input 1
17
Input 2
18
Input 3/Pulse input
1
The indicated outputs are dedicated for control when enabled in the loop setup. If one or both of a loop’s outputs are
disabled, the corresponding digital outputs become available for alarms or ramp/soak events.
2
For Watlow Serial DAC, the CLS200 series controller uses digital output 34 for a clock line. You cannot use output 34 for
anything else when you have a control output configured for the SDAC.