![Watlow CLS200 Скачать руководство пользователя страница 36](http://html1.mh-extra.com/html/watlow/cls200/cls200_user-manual_3708024036.webp)
CLS200 Series User’s Guide
Chapter 2: Installation
36
Pulse Input
Com
Encoder
+5VDC
10kΩ
CLS200 and TB50 or TB18
Figure 2.17
— Encoder with 5VDC TTL Signa
Pulse Input
Com
Encoder
+5VDC
10kΩ
R2
R1
Figure 2.18
— Encoder Input with Voltage Divider
For encoders with signals greater than 5VDC, use a voltage divider to drop the voltage to 5 volts at
the input. Use appropriate values for R1 and R2 depending on the encoder excitation voltage. Be
sure not to exceed the specific current load on the encoder.
Wiring Control and Digital I/O
This section describes how to wire and configure the control outputs for the CLS200 series
controller.
NOTE!
Control outputs are connected to the CLS200’s common when the control output
is on (low). Be careful when you connect external devices that may have a low side at a
voltage other than controller ground, since you may create ground loops.
If you expect grounding problems, use isolated solid state relays and isolate the control
device inputs.
The CLS200 provides dual PID control outputs for each loop. These outputs can be enabled or
disabled, and are connected via TB50 or TB18.
Output Wiring Recommendations
When wiring output devices, use multicolored, stranded, shielded cable for analog outputs and digital
outputs connected to panel-mounted solid state relays.
• Analog outputs usually use a twisted pair.
• Digital outputs usually have 9 to 20 conductors, depending on wiring technique.