CHARACTERISTIC
OPTIONS
DESCRIPTION
Analog Input 1
Options for all units:
• Standard (Thermocouples and
-10 to 60mV)
• Linear Current: 0-20mA DC /
4-20mA DC
• Linear Voltage: 0-5VDC
• Linear Voltage: 0-10VDC
Additional options for 4-loop and
8-loop units:
• 100 Ohm RTD Tenths Degree
• 100 Ohm RTD Whole Degree
Standard units accept thermocouples on
all inputs. Controllers can be equipped with
resistors to scale signals for various types
of sensors. These resistors must be factory
installed.
Sixteen loop controllers cannot accept RTD
sensors.
Analog Input 2
Analog Input 3
Analog Input 4
Analog Input 5
Analog Input 6
Analog Input 7
Analog Input 8
Analog Input 9
Analog Input 10
Analog Input 11
Analog Input 12
Analog Input 13
Analog Input 14
Analog Input 15
Analog Input 16
Technical Description
This section contains a technical description of each component of your CLS200 series controller.
CLS200
The CLS200 is housed in an 1/8-DIN panel mount package. It contains the CPU, RAM with a built-in
battery, EPROM, serial communications, digital I/O, analog inputs, the screen and touch keypad.
SCSI Digital I/O Option
TB18 Digital I/O Option
Figure 1.1
— CLS200 Rear Views
The CLS200 has the following features:
• Keypad and 2-line, 16-character display.
• Screw terminals for the power and analog inputs and communications.
• Input power is 12 to 24VDC at 1 Amp.
• A 50-pin SCSI cable connects the digital inputs and outputs to the 50-terminal block (TB50).
Four-loop and eight-loop models are available with an 18-terminal block (TB18) in place of the
SCSI connector, as shown in