CLS200 Series User’s Guide
Chapter 8: Troubleshooting and Reconfiguring
148
4. Connect the voltmeter’s common lead to the output terminal, and connect the voltmeter’s
positive lead to the +5V terminal.
5. Restore power to the controller.
6. If you are testing a PID control output, use the
MAN/AUTO
key to turn the output on (100%)
and off (0%). When the output is off, the output voltage should be less than 1V. When the
output is on, the output voltage should be b3.75 and +5.25V.
7. If you are testing a digital output not used for control, use the
MANUAL I/O TEST
menu to
turn the output on and off. See
.
Testing Digital Inputs
1. Turn off power to the controller.
2. Disconnect any system wiring from the input to be tested.
3. Restore power to the controller.
4. Go to the
DIGITAL INPUTS
parameter in the
MANUAL I/O TEST
menu. This parameter
shows whether the digital inputs are
H
(high, or open) or
L
(low, or closed).
5. Attach a wire to the terminal of the digital input to test. When the wire is connected only to
the digital input terminal, the
DIGITAL INPUTS
parameter should show that the input is
H
(high). When you connect the other end of the wire to controller common (TB50 terminal 3), the
DIGITAL INPUTS
parameter should show that the input is
L
(low).
Additional Troubleshooting for Computer Supervised Systems
These four elements must work properly in a computer-supervised system:
• The controller
• The computer and its EIA/TIA-232 or EIA/TIA-485 serial interface
• The EIA/TIA-232 or EIA/TIA-485 communication lines
• The computer software
For troubleshooting, disconnect the communications line from the computer and follow
the troubleshooting steps in the first section of this chapter. The next few sections explain
troubleshooting for the other elements of computer supervised systems.
Computer Problems
If you are having computer or serial interface problems, check the following:
• Check your software manual and make sure your computer meets the software and system
requirements.
• Check the communications interface, cables, and connections. Make sure the serial interface
is set according to the manufacturer’s instructions.
• To test an EIA/TIA-232 interface, purchase an EIA/ TIA-232 tester with LED indicators. Attach
the tester between the controller and the computer. When the computer sends data to
the controller, the tester’s TX LED should blink. When the computer receives data from the
controller, the RX LED should blink.