CLS200 Series User’s Guide
Chapter 8: Troubleshooting and Reconfiguring
147
• Verify which type of sensor is installed and that the
INPUT TYPE
parameter is set
accordingly.
• For an RTD or linear voltage or current input, check that the correct input scaling resistors are
installed (see
) and check the input scaling parameter settings
(see
Linear Scaling Parameters on page 77
).
• If readings are erratic, look for sources of electrical noise. See
• Eliminate possible ground loops. See
.
• Contact your supplier for further troubleshooting guidance.
Checking Control Outputs
To check control outputs:
• Set the loop you want to check to manual mode.
• Set the output power percentage to the desired level.
• Set the output type to
ON/OFF
or
TP
If the control output is not connected to an output device like an SSR, connect an LED in series with
a 1 kW resistor from +5V to the output. (Tie the anode of the LED to +5V.) The LED should be off
when the output is 0% and on when the output is 100%.
Testing Control Output Devices
Connect the solid state relay (SSR) control terminals to the CLS200 control output and connect a
light bulb (or other load that can easily be verified) to the output terminals on the SSR. Put the loop
in manual mode and set the output to 100%. The ac load should turn on.
Do not attempt to measure ac voltage at the SSR’s output terminals. Without a load connected,
the SSR’s output terminals do not turn off. This makes it difficult to determine whether the SSR is
actually working. Measure the voltage across a load or use a load that can be visually verified, such
as a light bulb.
Testing the TB18 and TB50
1. Turn on power to the controller.
2. Measure the +5VDC supply at the TB18 or TB50. The voltage should be +4.75 to +5.25VDC:
a. Connect the voltmeter’s common lead to the TB18 screw terminal 2 or TB50 screw
terminal 3.
b. Connect the voltmeter’s positive lead to the TB18 or TB50 screw terminal 1.
Testing Control and Digital Outputs
1. Turn off power to the controller.
2. Disconnect any process output wiring on the output to be tested.
3. Connect a 500Ω to 100kΩ resistor between the +5V terminal (TB18 or TB50 screw
terminal 1) and the output terminal you want to test.