CLS200 Series User’s Guide
Chapter 5: Enhanced Features
114
To set up this application, you would do the following:
1. Change the display to loop 2, and then enter the setup parameters. Go to the first screen in
Table 5.5
.
2. Follow the steps in
Table 5.5
to configure the process variable retransmit option.
Table 5.5
—
Application Example: Setting Up Differential Control
DISPLAY
USER INPUT
ALARM
SETUP LOOP 02
RATIO CONTROL?
Press
YES
to set up the cascade parameters with loop 2.
ALARM
02 RATIO CONTROL
MSTR LOOP? 01
Assign loop 01 as the master loop. Press
ENTER
.
ALARM
02 RATIO CONTROL
MIN SP? 300.0
Enter the minimum ratio loop setpoint. For this example, we
will use
300.0
˚ F. Press
ENTER
.
ALARM
02 RATIO CONTROL
MAX SP? 400.0
Enter the maximum ratio loop setpoint. For this example, we
will use
400.0
˚ F. Press
ENTER
.
ALARM
02 RATIO CONTROL
CTRL RATIO? 1.0
Enter the control ratio, which is the multiple applied to the
master process variable. In this example the ratio is
1.0
.
Press
ENTER
.
ALARM
02 RATIO CONTROL
SP DIFF.? 50
Enter the setpoint differential (or offset). For this example, we
have an offset of
+50
. Press
ENTER
.
3. Press
BACK
several times until the normal loop display appears. The setpoint of loop 2 will
now be equal to process variable of loop 1 plus 50°F.
4. To complete the differential control setup, loop 1 and loop 2 must be configured for inputs,