![Watlow 97 series Скачать руководство пользователя страница 80](http://html1.mh-extra.com/html/watlow/97-series/97-series_user-manual_3705918080.webp)
A . 1 8
■
A p p e n d i x
Wa t l o w S e r i e s 9 7
Electromechanical Relay
• Form C contact configuration
• Minimum load current 10mA @ 5V
Î
(dc)
• Rated resistive and inductive loads: 2A @ 250V
Å
(ac) or
30V
Î
(dc) maximum
• Electrical life 100,000 cycles at rated current
• For resistive loads only, must use RC suppression for
inductive loads
Retransmit
• Range selectable: 0-20mA, 4-20mA, 0-5V
Î
(dc),
1-5V
Î
(dc), 0-10V
Î
(dc)
• 0 to 10V
Î
(dc) voltage output into a 1,000
Ω
minimum load
resistance
• 0 to 20mA current output into an 800
Ω
maximum load
resistance
• Resolution:
dc ranges = 2.5mV nominal
mA ranges = 5µA nominal
• Calibration accuracy:
dc ranges = ±10mV
mA ranges = ±20µA
• Temperature stability 100ppm/°C
Specifications
(1135)
Controller
• Microprocessor-based, user selectable control modes
• Input sample period; Single input 10Hz (100 msec), dual input
5Hz (200 msec) digital filter adjustable
• Display update; 2Hz (500 msec), time filter adjustable
• Input/Output/Communication isolation
• Displayed in °C or °F
Operator Interface
• Dual 4-digit LED displays: upper 0.4 in (10.2 mm), lower
0.244 in (6.2 mm)
• Advance, Up Arrow, Down Arrow, Reset tactile keys
Standard Conditions For Specifications
• Ambient temperature 77°F/25°C ±3°C, rated line voltage, 50 to
60Hz, 0 to 90% RH non-condensing,
15 minute warm-up
Universal Input 1
Thermocouple
• Type J, K, T, N, C (W5), E, PTII, D (W3), B, R, S thermocouple
types
• >20M
Ω
input impedance
• Maximum 20
Ω
source resistance
• 30mA open detection bias
RTD
• 2- or 3-wire platinum, 100
Ω
• JIS and DIN curves
• Whole or tenth degree indication
• 150µA nominal RTD excitation currrent
Input 2
Event Input
• Contact or voltage
• 20K
Ω
input impedance
• Voltage input: event high state 3 to 36V
Î
(dc),
event low state 0 to 2V
Î
(dc)
• Resistance/contact input: event high state > 23k
Ω
, event low
state 0 to 2k
Ω
Output Types
Open Collector/Switched DC
• Open collector configuration:
Maximum voltage 42V
Î
(dc)
Maximum current 200mA
Maximum “on” resistance 0.15
Ω
Maximum offstate leakage current 100µA
• Switched dc configuration:
Switched dc supply voltage 22 to 28V
Î
(dc)
dc supply current limited to 30mA
Solid-State Relay
• Optically isolated
• Zero cross switched
• Without contact suppression
• Minimum load current 0.5mA rms
• Maximum current 0.5A rms at 20 to 280V
Å
(ac)
• Maximum offstate leakage current 10µA rms
• For resistive loads only, must use RC suppression for inductive
loads
Содержание 97 series