Wa t l o w S e r i e s 9 7
A p p e n d i x
■
A . 1 1
Calibrating the Series 97
To enter the a calibration menu, first warm up the unit, then enter the Factory
Page by holding down the Reset Key and
‰
for six seconds. Once in the Factory
Page
[Fcty]
use the up-arrow
¿
or down-arrow
¯
key to select a menu. The
last two menus on the Factory Page are Input Calibration Menu
[cin1]
and
Output Calibration Menu
[cout]
. If
[`Ot4]
is not a process output, the
[cout]
prompt will not appear.
You can restore the original factory calibration with Restore Factory Calibration
[`rSt]
(Calibration 1 Menu) or revert to the default parameter range value
with Default Settings
[dFLt]
(Calibration 1 Menu).
Figure A.11 — The Calibration Menus.
Factory Page
[Fcty]
Factory Page
[`rSt]
Restore Factory Calibration
[dFLt]
Default Settings
[tc50]
Thermocouple Calibration, 50mV
[tc00]
Thermocouple Calibration, 0mV
[tc32]
Thermocouple Calibration, 32mV
[`gnd]
Set Ground
[LEAd]
Lead Resistance Calibration
[r`15]
RTD Calibration, 15
Ω
[r380]
RTD Calibration, 380
Ω
[Fcty]
Factory Page
[4``4]
Output Calibration 4, 4mA
[4`20]
Output Calibration 4, 20mA
[4``1]
Output Calibration 4, 1V
[4`10]
Output Calibration 4, 10V
‰
¿
[`LOC]
Lockout Menu
[FctY]
[dIAg]
Diagnostics Menu
[FctY]
[cin1]
Input Calibration Menu
[FctY]
‰
[cout]
Output Calibration Menu
[FctY]
¯