NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.
Active if Calibration Lock
(Lockout Menu) is not set to
[hide]
1603 w
[``no]
[``no]
no (0)
[`yes]
yes (7)
[r380]
RTD Calibration,
380
Ω
Stores 380.00
Ω
calibration for input
1 RTD.
Active if Calibration Lock
(Lockout Menu) is not set to
[hide]
1603 w
[``no]
[``no]
no (0)
[`yes]
yes (6)
[r`15]
RTD Calibration,
15
Ω
Stores 15.00
Ω
calibration for input
1 RTD.
Active if Calibration Lock
(Lockout Menu) is not set to
[hide]
1603 w
[``no]
[``no]
no (0)
[`yes]
yes (5)
[Lead]
Lead Resistance
Calibration
Stores calibration
for lead resistance.
Active if Calibration Lock
(Lockout Menu) is not set to
[hide]
1603 w
[``no]
[``no]
no (0)
[`yes]
yes (4)
[`gnd]
Set Ground
Stores calibration for
ground at gains of 1
and 32.
Active if Calibration Lock
(Lockout Menu) is not set to
[hide]
1603 w
[``no]
[``no]
no (0)
[`yes]
yes (3)
[tc32]
Thermocouple
Calibration, 32º
Stores 32 degrees F
type J calibration.
Active if Calibration Lock
(Lockout Menu) is not set to
[hide]
1603 w
[``no]
[``no]
no (0)
[`yes]
yes (1)
[tc00]
Thermocouple
Calibration, 0mV
Stores 0.000mV
calibration for input
1 thermocouple.
Active if Calibration Lock
(Lockout Menu) is not set to
[hide]
1603 w
[``no]
[``no]
no (0)
[`yes]
yes (2)
[tc50]
Thermocouple
Calibration, 50mV
Stores 50.000mV
calibration for input
1 thermocouple.
Active if Calibration Lock
(Lockout Menu) is not set to
[hide]
1602 w
[``no]
[``no]
no (0)
[`yes]
yes (800)
[dflt]
Default Settings
Restores default
settings.
Active if Calibration Lock
(Lockout Menu) is not set to
[hide]
1601 w
[``no]
[``no]
No (0)
[`yes]
Yes (1)
[`rSt]
Restore Factory
Calibration
Restores factory
calibration (Stores
factory calibration
with special key
sequence).
[cin1]
Input Calibration
Menu
[Fcty]
Factory Page
6 . 2 0
■
P a r a m e t e r s
Wa t l o w S e r i e s 9 7
Factor
y Page / Calibration 1 Menu
Display
Parameter
Range
Default
Modbus
Conditions for
Address
Parameters to Appear
read/write