Event Input
With an event input an operator can perform certain operations on a system by opening or
closing a switch or applying a dc logic signal to the controller. This feature can add conve-
nience, safety or security to a system.
Use Event Input Status
[E`St]
(Monitor Menu) to read the state of the event input para-
meter.
Use Event Function
[E`Fn]
(Input 2 Menu) to select how an event will affect the system.
[nonE]
Events will not affect the system.
[Lrst]
Clear Limit.
[`LOC]
Lock out key board.
[ALr`]
Clear an alarm.
Use Event Condition
[E`cn]
(Input 2 Menu) to select what condition will trigger an event.
[``Lo]
Low generates an event while the voltage is low (switch closed).
[``hi]
High generates an event while the voltage is high (switch open).
[riSE]
Rise changes the event state when the voltage changes from low to high.
[FALL]
Fall changes the event state when the voltage changes from high to low.
Figure 5.6 — Event inputs.
Time
V
oltage
Low Event
(switch closed)
High Event
(Switch open)
Rise Event
Fall Event
5 . 6
■
F e a t u r e s
Wa t l o w S e r i e s 9 7
Содержание 97 series
Страница 10: ...Notes 2 4 Installation Watlow Series 97...
Страница 22: ...3 12 Wiring Watlow Series 97 Notes...
Страница 40: ...5 12 Features Watlow Series 97 Notes...