Watlow EZ-ZONE
®
PM Integrated Controller
•
90
•
Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[`A;hi]
[ A.hi]
Alarm (1 to 4)
Alarm High Set Point
If Alarm Type (Setup
Page, Alarm Menu) is
set to:
process
- set the process
value that will trigger
a high alarm.
deviation
- set the span
of units from the closed
loop set point that will
trigger a high alarm.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
300.0°F
or units
150.0°C
Instance 1
Map 1 Map 2
1480 1880
Offset to next
instance (
Map
1
) 50
Offset to next
instance (
Map
2
) 60
0x6D
(109)
1 to 4
1
19
9001
float
RWES
[`A;LA]
[ A.LA]
Alarm (1 to 4)
Alarm Latching
Turn alarm latching on
or off. A latched alarm
has to be turned off by
the user.
[nLAt]
Non-Latching (60)
[`LAt]
Latching (49)
Non-
Latching
Instance 1
Map 1 Map 2
1492
1892
Offset to next
instance (
Map
1 50,
for Map 2
60)
0x6D (109)
1 to 4
7
27
9007
uint
RWES
[`A;bL]
[ A.bL]
Alarm (1 to 4)
Alarm Blocking
Select when an alarm
will be blocked. After
startup and/or after the
set point changes, the
alarm will be blocked
until the process value
enters the normal range.
[`oFF]
Off (62)
[`Str]
Startup (88)
[StPt]
Set Point (85)
[both]
Both (13)
Off
Instance 1
Map 1 Map 2
1494 1894
Offset to next
instance (
Map
1 50,
for Map 2
60)
0x6D (109)
1 to 4
8
28
9008
uint
RWES
[`A;Si]
[ A.Si]
Alarm (1 to 4)
Alarm Silencing
Turn alarm silencing on
to allow the user to dis-
able this alarm.
[`oFF]
Off (62)
[``on]
On (63)
Off
Instance 1
Map 1 Map 2
1490
1890
Offset to next
instance (
Map
1 50,
for Map 2
60)
0x6D (109)
1 to 4
6
29
9006
uint
RWES
[A;dSP]
[A.dSP]
Alarm (1 to 4)
Alarm Display
Display an alarm mes-
sage when an alarm is
active.
[`oFF]
Off (62)
[``on]
On (63)
On
Instance 1
Map 1 Map 2
1510
1910
Offset to next
instance (
Map
1 50,
for Map 2
60)
0x6D (109)
1 to 4
0x10 (16)
30
9016
uint
RWES
[`A;dL]
[ A.dL]
Alarm (1 to 4)
Alarm Delay Time
Set the span of time that
the alarm will be delayed
after the process value
exceeds the alarm set
point.
0 to 9,999 seconds
0
Instance 1
Map 1 Map 2
1520
1920
Offset to next
instance (
Map
1 50,
for Map 2
60)
0x6D (109)
1 to 4
0x15 (21)
31
9021
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
R: Read
W: Write
E:
EEPROM
S:
User
Set