Graphical Digital Panel Meter WPMZ-1 INSTRUCTION MANUAL
50
IM-0882-03
Even if you only use terminals 1 and 2, you can select pattern 1 or 2 or 3 or 4.
*Functions not assigned to external control terminals are treated as “open”.
Function
Selected Pattern
1
2
3
4
5
6
7
8
PatternChange1
Open
Short
Open
Short
Open
Short
Open
Short
PatternChange
2
Open
Open
Short
Short
Open
Open
Short
Short
PatternChange
3
Open
Open
Open
Open
Short
Short
Short
Short
Open: Open the terminal or set to “1” level.
Short: Short the terminal with “COM” terminal or set to “0” level.
CAUTION
When the pattern is switched, the measurement data before switching is cleared and
measurement starts from the switching point.
Setting Items
DispHoldMode
You can switch the operating mode of DispHold either “FreeRun” or “OneShot”.
FreeRun: The display value is held while the external control terminal is set to low level.
OneShot: The display value is kept constant all the time, and it is updated every time
the external control terminal falls.
For details, please refer the content about “DispHold”.
Operation: [MENU]
⇒
[Input]
⇒
[HoldA] [HoldB]
⇒
[DispHoldMode]
Setting value: Normal (Default), OneShot
HoldOffDelay
You can set the delay about when the DispHold function is canceled.
There are differences in the delay operation for each “FreeRun” and “OneShot” shown below.
“FreeRun”: You can set the time from release of device to release of hold.
“OneShot”: You can set the time from release of device to update of display value.
This function is disable when the setting value is 0.
Operation: [MENU]
⇒
[Input]
⇒
[HoldA] [HoldB]
⇒
[HoldOffDelay]
Setting value:0
~
99.99[sec]
(Default is 0)
CAUTION
Setting of retention cancellation delay is effective only for "DispHold".
No delay occurs when releasing other holding functions.
HoldMode
You can switch the operation mode of each holding function except "DispHold" function to "NormalHold" or
"AreaHold".
The basic operation of each mode is as follows.
"NormalHold": The hold function is executed while the terminal is short-circuited and released when the
terminal is released
"AreaHold": The hold function is executed while the terminal is short-circuited, and the display value is fixed
with the final
holding value when the terminal is released
For details of operation of each holding function, please confirm the holding function explanation.
Operation: [MENU]
⇒
[Input]
⇒
[HoldA] [HoldB]
⇒
[HoldMode]
Setting value: NormalHold(Default), AreaHold