■Meaning of warning mark 

 
 
 

 
■Caution marks 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

(1)The application of voltage or current exceeding its maximum 

allowable value to the input terminals may result in instrument 
damage. 

(2)The supply of power out of its allowable range may cause fire, 

electric shock or instrument failure. 

(3)The content of this manual may subject to change without prior 

notice for product improvement. 

(4)This manual is carefully prepared. However, if any question  

arises, or any mistake, omission or suggestion is found in the 
content of this manual, contact your nearest our sales agent. 

  (5)Make this manual available easily anytime. 

 

 
 

 
 

 
 
 
 
1.Outline 

The AP-212 digital meter relay is a scaling meter with the 2-step 

setting analog  comparator function. It  is provided  with  the 

output  of  2-stage  relays  and  analog  signal  as  the  standard 

specification. It has case dimensions of 48mm×24mm conforming 

to DIN Standard and is driven by a power supply voltage of 24V 

DC. 

Its display uses 7-segment LEDs with a character height of 8mm 

with a maximum display of 1999. 

 
 
 
 
 

 

 
 
 
 
 

2.

Specifications 

■Instrumentation signal input 

  (DC voltage measurement) 

Accuracy:±(0.1% of rdg +2digit)(23℃±5℃、35 to 85%RH) 

■Instrumentation signal input 

(DC current measurement) 

Accuracy:±(0.1% of rdg +2digit)(23℃±5℃、35 to 85%RH) 

■DC voltage measurement 

Accuracy:±(0.1% of rdg +2digit)(23℃±5℃、35 to 85%RH) 

■DC current measurement 

  Accuracy:±(0.2% of rdg +2digit)(23℃±5℃、35 to 85%RH) 

    However, only for the AM-212-25: ±(0.3% of rdg +1digit) 

    *In the internal resistance column: Externally mounted. 

 
■Model No. configuration 
   Example: 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Model/Range 

code 

Measuring 

range 

Display 

Input 

impedance 

Max. allowable 

input voltage 

AM-212-1V 

1 to 5V 

Offset ±1000 

Fullscale 

100 to 1999 

Approx.1MΩ 

±250V 

Model/Range 

code 

Measuring 

range 

Display 

Input 

resistance 

Max. 

allowable 

input current 

AM-212-2A 

4 to 20mA 

Offset ±1000 

Fullscale  

100 to 1999 

51Ω 

±70mA 

Model/Range 

code 

Measuring 

range 

Display 

Input 

impedance 

Max. allowable 

input voltage 

AM-212-11 

±199.9mV 

 Offset  ±1000 

 

Fullscale       

±100 to 1999 

100MΩ 

±100V 

AM-212-12 

±1.999V 

10MΩ 

±250V 

AM-212-13 

±19.99V 

10MΩ 

±250V 

AM-212-14 

±199.9V 

10MΩ 

±500V 

Model/Range 

code 

Measuring 

range 

Display 

Input 

resistance 

Max. allowable 

input current 

AM-212-21 

±199.9μA 

Offset ±1000 

 

Fullscale       

±100 to 1999 

1kΩ 

±10mA 

AM-212-22 

±1.999mA 

100Ω 

±50mA 

AM-212-23 

±19.99mA 

10Ω 

±150mA 

AM-212-24 

±199.9mA 

※1Ω 

±500mA 

AM-212-25 

±1.999A 

※0.1Ω 

±3A 

DIGITAL METER RELAY

 

INSTRUCTION MANUAL

 

MODEL AM-212 SERIES

 

Precautions 

This mark indicates that if the meter is 
operated incorrectly, death or serious 
injury may result. 

WARNING 

Do not disassemble the meter or touch the components 
and parts inside the meter with the power turned on 
or input connected. 

CAUTION 

The mark on the label indicates the measuring range 
in Item 2. Specifications. 

Caution required when the AM-212 is used on equipment conforming 

to EN/IEC Standards! 

For the AM-212 with an input signal of more than 70VDC, connect its 

HOLD and ANALOG out terminals to the equipments whose foundation 

is isolated. 