rated output can be replaced by 2 times 30 minute engine operation at 70 % of the rated
output. Note that shorter duration than 30 minutes is not recommended.
2.4
Low air temperature
The minimum inlet air temperature of 5°C applies, when the inlet air is taken from the engine
room.
Engines can run in colder conditions at high loads (suction air lower than 5°C) provided that
special provisions are considered to prevent too low HT-water temperature and T/C surge.
For start, idling and low load operations (Ch 2.3), suction air temperature shall be maintained
at 5°C.
If necessary, the preheating arrangement can be designed to heat the running engine (capacity
to be checked).
For further guidelines, see chapter Combustion air system design.
DAAB605814
2-5
2. Operating Ranges
Wärtsilä 46F Product Guide
Содержание 46F Series
Страница 1: ...Wärtsilä 46F PRODUCT GUIDE ...
Страница 4: ...This page intentionally left blank ...
Страница 8: ...This page intentionally left blank ...
Страница 18: ...This page intentionally left blank ...
Страница 46: ...Fig 4 3 Cross section of the V engine 4 6 DAAB605814 Wärtsilä 46F Product Guide 4 Description of the Engine ...
Страница 86: ...This page intentionally left blank ...
Страница 104: ...This page intentionally left blank ...
Страница 154: ...This page intentionally left blank ...
Страница 162: ...This page intentionally left blank ...
Страница 170: ...This page intentionally left blank ...
Страница 176: ...This page intentionally left blank ...
Страница 194: ...This page intentionally left blank ...
Страница 200: ...This page intentionally left blank ...
Страница 202: ...This page intentionally left blank ...
Страница 207: ...Fig 21 7 List of symbols DAAF406507 7 DAAB605814 21 5 21 ANNEX Wärtsilä 46F Product Guide ...